Adjust and Function Specification
§
Cd64 Dynamic braking range (Settable range 0-1)
This function cannot be adjusted during revolution.
Cd64 = 0 Dynamic braking can be active during acceleration, deceleration and
constant speed.
Cd64 = 1 Dynamic braking can be active during acceleration and deceleration, but
not active during constant speed operation.
§
Cd65 Instant initial field time (Settable range 1-7)
This function cannot be adjusted during revolution
This function is to adjust instant initial field current of motor. Shorter of the time,
higher of the field current .
Cd 65
Instant initial field time
1
64 ms
2
128 ms
3
256 ms
4
512 ms
5
1024 ms
6
2048 ms
7
4096 ms
Output
Frequency
Set frequency
DC braking frequency
in stopping
Cd24
Start frequency
Cd16
t
DC braking time in starting
Cd23,Cd26
Output
voltage
Instant
initial
field time
Cd65
DC braking time in stopping
Cd23,Cd26
Output voltage of
set frequency
Output voltage of
start frequency
DC braking voltage
Cd25
t