Adjust and Function Specification
2. Restart after instantaneous power failure
This function if different from free run restart, the inverter control power is maintained
above 5V.
Restart after instantaneous
power failure: no function
Restart after instantaneous
power failure: with function
Power Supply
External Switch
Inverter Power
Motor Speed
When it detects low voltage “PLU”, it activates
“STOP”, “PLU”. After recovery of voltage, “PLU”
are de-active, “STOP” remains the same, and it
will have to switch “ON” again to restart if you
select external control, if you select panel
control, just press “FWD” or “REW” key to
restart.
Restart motor under free run.
Instantaneous power
failure, Voltage loss
15msec.
Note: The inverter will be de-active when control voltage is less than 5V.
Apply with free run restart function when it is required.
§
Cd29 Time (Settable range 0-9000)
This function must accommodate Cd47=0 setting.
When motor starts operation, the time counter is active.
§
Cd30 Stop by panel key (Settable range 0-1)
Cd30=0 No function
Cd30=1 With function
Stop function: This function enables the inverter to be stopped by panel