Adjust and Function Specification
§
Cd46
Speed multiplier
(Settable range 0.01-500)
The function shows revolution speed multiplied by a scaling factor on the Display.
Note:
1. HZ and A LED de-active.
2. RPM = Frequency
×
Cd46
3. If the value overflow, it will show “9999”.
§
Cd47 Relay 1 output select (Settable range 0-6)
The function sets the mode of relay1 to activate.
Cd47
Specification
Remark
0
Time counter
Time reached to the content of Cd29
1
Fault
2
Stop
3
Acceleration
4
Speed reached
5
Deceleration
6
Speed pass over
Revolution frequency
>
content of Cd45
§
Cd48 Relay 1 output select (Settable range 0-6)
The function sets the mode of relay2 to activate.
Cd47
Specification
Remark
0
Time counter
Time reached to the content of Cd29
1
Fault
2
Stop
3
Acceleration
4
Speed reached
5
Deceleration
6
Speed pass over
Revolution frequency
>
content of Cd45
§
Cd49 Function to lock data (Settable range 0, 1)
To lock data, prevent errors by none operator.
Cd49=0 Data change capable