Wireless Adapter (WA100-PM)

i. Installation Instructions

The Daintree WA100-PM Wireless Adapter forms part of the Daintree ControlScope wireless controls solution for smart 
commercial and industrial buildings. It transmits and receives messages over the wireless ZigBee

®

 network and controls lights. 

The WA100-PM is an AC powered device that provides On/Off switching as well as 0-10V analog dimming control for 
LED drivers and ballasts.* It also provides power for low voltage occupancy sensors, photosensors (daylight harvesters), 
wall switches, and control signals while it provides the wireless adaptation that enables them to communicate with the 
rest of the wireless control solution. The control signals to and from these connected devices pass between the WA100-PM 
and the Wireless Area Controller in ControlScope Manager (CSM), the Daintree management app.

Installation Process 

1. Disconnect power before installation. Turn off all
power to affected light fixtures by turning off circuit
breakers. Confirm that power is off at all light fixtures
before continuing installation.

2. Set the WA100-PM DIP switches to support the device(s)
being connected to it. See 

DIP Switch Settings

 (pages 2-3).

3. IMPORTANT: Affix the small label with 4-5 digits of the
WA100-PM’s IEEE address on the floor Plan to indicate
its location.

4. Mount the WA100-PM in the driver cavity of the light
fixture, or external to the light fixture, or to a junction box
approved for the application. See 

Mounting

 (page 13).

5. Connect low voltage wiring from the WA100-PM to the
driver, switch(es) and/or sensors as appropriate for your
application. See 

Wiring

 (pages 4-11). Cap any unused wires.

6. Connect line voltage wires from the supply circuit to the
WA100-PM and to the driver as shown in 

Wiring.

 Cap any

unused wire.

7. Check load circuits then turn on the circuit breakers
to power up the WA100-PM. The light connected to the
WA100-PM turns On when power is initially applied (and
when power is restored after a power failure).

8. Ensure the WA100-PM green Power      LED is On.

9. Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button when the
green Joined      LED and the red Error      LEDs begin flashing.

10. Perform the installation test appropriate for your
application. See 

Installation Tests

 (pages 14-16) .

RESET

Error

 

Joined

 

Power

 

Reset

LED

 

LED

 

LED

 

Error—On when the Wireless Adapter is in an error state. 
Flashes once per second to indicate DIP Switch 
configuration error. Flashes to indicate unit Reset 
and during Installation Test Mode  (red).

Joined—On when the Wireless Adapter has joined a 
ZigBee

®

 network. Flashes to indicate Reset and during 

sensor Installation Test Mode (green).

Power—On when power is applied to the Wireless 
Adapter (green).

LED Indicators

1

DT11

3

 (Rev. 1

2

.

8

.17)

Summary of Contents for WA100-PM

Page 1: ...n to indicate its location 4 Mount the WA100 PM in the driver cavity of the light fixture or external to the light fixture or to a junction box approved for the application See Mounting page 13 5 Conn...

Page 2: ...xpected operation After you change DIP switch settings you need to press the blue Reset button for 3 seconds to reset the unit Release the button when the green Joined and red Error LEDs begin flashin...

Page 3: ...0 See Figure 12 No Driver sensors only provides wireless adaptation to connected occupancy sensor and or photosensor only No driver control Sensor To provide wireless adaptation for sensors set DIP sw...

Page 4: ...Line voltage wiring connects to the electrical supply circuit and to the driver s The Black Hot flying lead and the Red Switched Load flying lead are 14AWG The White Neutral flying lead is 18AWG Low v...

Page 5: ...7 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM 15A 15A 45mA...

Page 6: ...cent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1...

Page 7: ...ature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow...

Page 8: ...DC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blu...

Page 9: ...ltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Te...

Page 10: ...e chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24V...

Page 11: ...ent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1h...

Page 12: ...Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 0...

Page 13: ...t Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Red Blue Digital In 1 Yellow Digital In 2...

Page 14: ...Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents...

Page 15: ...A Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digi...

Page 16: ...s Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDO...

Page 17: ...75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue D...

Page 18: ...57 CAN ICES 3 B NMB 3 B RoHS WA100 PM REGULAR Line Voltage 120 277VAC LVS Model RRU X UM NC COM NO WHITE Neutral Hot NC COM NO RED BLACK BLUE RED BLUE YELLOW Connect 120VAC to BLK 277VAC to ORG FIXTUR...

Page 19: ...r LED Driver 0 10VDC WA100 PM Wireless Adapter WA100 PM Set DIP switches and perform Installation Test appropriate to 0 10v dimming and connected sensors In this application the WA100 PM is powered by...

Page 20: ...eep them neat out of the way and protected against shorting or interference with other components wiring or devices It is best to trim unused wires to about 5 inches in length isolate them using a wir...

Page 21: ...The WA100 PM can be secured at the other end using the integral screw tab Alternatively it can be mounted externally to a junction box enclosure or fixture housing through a 1 2 knockout Fig 19 Mounti...

Page 22: ...aves significant time during the commissioning process Record IEEE Addresses If you have not already done so be sure that each WA100 PM s IEEE address last 4 or 5 digits is recorded on the facility fl...

Page 23: ...and repeats 2 Check that the lights connected to the driver cycle from maximum to minimum brightness then turn Off then repeat 3 Press and immediately release the blue Reset button The red Error LED f...

Page 24: ...it testing 4 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when the green Joined LED and the red Error LEDs begin flashing Test Suite 6 Photos...

Page 25: ...sor the light turns On 6 Press and immediately release the Reset button to exit testing 7 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when t...

Page 26: ...e Manager application Troubleshooting The Installation Test procedure fails 1 Confirm that the WA100 PM is powered 2 Check the connections from the WA100 PM to the driver s and low voltage control dev...

Page 27: ...L x 1 7 W x 1 18 H 10 1 L x 1 7 W x 1 18 H with mounting bracket Driver references include ballasts unless otherwise noted FCC warning message This equipment has been tested and found to comply with t...

Page 28: ...t 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red Whit...

Page 29: ...o 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0...

Page 30: ...ss 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM...