GG-H2-EC

Operation

Start-Up

Before applying power, make a final check of all wiring 

for continuity, shorts, grounds, etc.  It is usually best 

to disconnect external alarms and other equipment 

from the sensor until the initial start-up procedures 

are completed.
After power-up, allow at least 1 hour for the system to 

stabilize before testing the sensors.  Because sensors 

are normally located at a distance from the main unit, 

the test time required and accuracy of the response 

checks will be improved if two people perform the 

start-up procedures and use radio contact.

Start-Up Test: 

1) One person exposes each sensor to hydrogen test 

gas. 

2) The second person stays at the control unit to 

determine that each sensor, when exposed to the 

gas, is connected to the proper input and responds, 

causing appropriate alarm functions.

Calibration

The GG-H2 Sensor comes factory calibrated and 

should require only minimal adjustments after 

installation. There are two pots on the preamp that 

are used for calibration.

Note:  Never measure sensor output in mA .  

Always use mVDC or VDC voltmeter settings .

Zero Calibration:

 After the unit is installed and has 

been powered up for a minimum of 12 hours, the unit 

can be zero calibrated by the following:
•  Be sure the unit is in clean air.
•  Adjust the zero pot until the sensor outputs 40 mV 

from Test [-] to Test [+] (see 

Figure 2

).

Span Calibration:

 The unit is factory calibrated and 

normally does not need to be spanned upon initial 

installation. DO NOT ADJUST THE SPAN POT WITHOUT 

CERTIFIED CALIBRATION GAS!  If span adjustment is 

required, the following procedure will span the unit:
•  Perform zero adjustment before spanning.
•  Apply span gas at 0.8 L/min (span gas must be in 

air, not nitrogen or other carrier).

•  Sensor should react to gas within 10 seconds
•  Once the output signal has peaked (or two minutes 

maximum) adjust the span pot until the correct 

output is achieved (see

 Figure 2

).

Note: Below are a few response characteristics which 

may be an indication that the gas sensor is at or near 

the end of its useful life. If any of these are observed, 

the cell should be replaced:
•  Slow response to / recovery from calibration gas.
•  Failure of the output to reach 50% of the calibration 

gas value prior to span adjustment.

•  Unable to achieve correct output during span 

adjustment. 

Summary of Contents for GG-H2-EC

Page 1: ...Installation and Operation Manual GG H2 EC HYDROGEN GAS SENSOR...

Page 2: ...nly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...ies 920 N Trade Winds Pkwy Columbia MO 65201 866 394 5861 Sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6...

Page 4: ...atmospheric variations The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant...

Page 5: ...p sensor and wire runs away from mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws s...

Page 6: ...or insulated stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections s...

Page 7: ...A Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure the...

Page 8: ...Red Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 se...

Page 9: ...nsors are installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical ce...

Page 10: ...26 12 AWG torque 4 5 lbs in Power green LED Blinks once per second for 60 seconds during power up If supply voltage is too low 10VDC or improperly grounded will blink once per second continuously Sta...