GG-H2-EC

General Description

Installation

The GG-H2 sensor is a +24 VDC, three-wire, 4/20 

mA sensor for hydrogen which utilizes proven 

electrochemical sensor technology for fast and 

accurate detection.  The GG-H2 provides real-time 

continuous monitoring of hydrogen concentrations 

accurately without false alarms.  Two ranges are 

available: 0-2,000 ppm and 0-10,000 ppm H2 (0-1% or 

0-25%LEL)

The GG-H2 provides an industry standard linear 4/20 

mA output signal compatible with most gas detection 

systems and PLCs.  The output signal is not affected 

by drastic temperature and moisture variations, or by 

other atmospheric variations.  

The transmitter circuit board is sealed in potting 

compound, protecting sensitive electronic 

components and copper tracing from corrosion.  The 

specially vented chemical-resistant polycarbonate 

enclosure protects the sensor from accidental 

damage, weather and direct hose-hits from clean-up 

crews.

Locating the sensor

One of the most important considerations when 

installing GG-H2 sensors is that they must be easily 

accessible for calibration and maintenance. 

Since hydrogen gas is lighter than air, the sensor 

should be located close to the ceiling.  This is where 

hydrogen gas will typically accumulate.  This mounting 

location will usually provide the best personnel and 

property protection.

As a general rule of thumb, try to mount sensors 

within 30 feet of potential leak sources.

Summary of Contents for GG-H2-EC

Page 1: ...Installation and Operation Manual GG H2 EC HYDROGEN GAS SENSOR...

Page 2: ...nly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...ies 920 N Trade Winds Pkwy Columbia MO 65201 866 394 5861 Sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6...

Page 4: ...atmospheric variations The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant...

Page 5: ...p sensor and wire runs away from mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws s...

Page 6: ...or insulated stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections s...

Page 7: ...A Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure the...

Page 8: ...Red Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 se...

Page 9: ...nsors are installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical ce...

Page 10: ...26 12 AWG torque 4 5 lbs in Power green LED Blinks once per second for 60 seconds during power up If supply voltage is too low 10VDC or improperly grounded will blink once per second continuously Sta...

Page 11: ...ir of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a pro...

Page 12: ...ctiengineering com 866 394 5861 GG H2 EC DOC1 0 20171207...

Reviews: