5

GG-H2-EC

Installation Guidelines:

•  Remove enclosure lid to access mounting holes.
•  Remove and discard protective cell cap
•  Always mount the sensor vertically. 
•  Must be easily accessible for calibration and 

maintenance.

•  Mount the sensor close to the potential leak source.
•  For optimum detection, mount sensor close to 

ceiling (1’ – 3’ below ceiling level).

•  Take air movement and ventilation patterns into 

account.

•  To prevent electrical interference, keep sensor and 

wire runs away from mercury vapor lights, variable 

speed drives, and radio repeaters.

•  Protect sensor from physical damage(forklifts, etc.).
•  If mounting on a wall with studs, the mounting 

screws should be screwed into the studs.

•  Never mount the sensor in CA (controlled 

atmosphere) rooms because normal atmospheric 

levels of oxygen are required for operation.

•  For highly critical locations more than one sensor 

should be installed in each room. 

•  Mount sensor enclosures through the mounting 

holes as shown in Figure 1.  Use the supplied 

self-tapping screws for mounting on sheet metal 

surfaces.

Figure 1: Mounting Dimensions

2.0"

6.5"

6.8"

7.75"

Summary of Contents for GG-H2-EC

Page 1: ...Installation and Operation Manual GG H2 EC HYDROGEN GAS SENSOR...

Page 2: ...nly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Page 3: ...ies 920 N Trade Winds Pkwy Columbia MO 65201 866 394 5861 Sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6...

Page 4: ...atmospheric variations The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant...

Page 5: ...p sensor and wire runs away from mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws s...

Page 6: ...or insulated stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections s...

Page 7: ...A Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure the...

Page 8: ...Red Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 se...

Page 9: ...nsors are installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical ce...

Page 10: ...26 12 AWG torque 4 5 lbs in Power green LED Blinks once per second for 60 seconds during power up If supply voltage is too low 10VDC or improperly grounded will blink once per second continuously Sta...

Page 11: ...ir of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a pro...

Page 12: ...ctiengineering com 866 394 5861 GG H2 EC DOC1 0 20171207...

Reviews: