CTC EcoLogic S
Brine pump
Auto (Auto/10 days/On)
After installation is complete, you can choose to run the
brine pump constantly for 10 days to remove air from
the system. The brine pump then enters "Auto" mode.
"On" means the brine pump runs constantly.
Only applies to liquid/water heat pumps.
Menu: "Installer / Settings / Communication".
3.3.3
Settings Communication
Settings can be made here to control the product with a
controlling system.
3.3.3.1
Settings Ethernet
DHCP
Yes (Yes/No)
"Yes" enables automatic connection to the network.
If "No", custom router settings (IP address, Netmask
and Gateway) as well as DNR setting must be made.
Auto DNR
Yes (Yes/No)
If "Yes", default DNR server settings are used. If "No",
custom DNR settings must be made.
SNTP server
Option for custom SNTP server settings.
Connection speed
100mbit
Connection speed is specified here.
The factory-set connection speed is 100 Mbps.
3.3.3.2 Settings BMS
MB address
1 (1...255)
Adjustable "1-255".
Baud rate
9600 (9600/19200)
Possible settings: "9600" or "19200".
Parity
Even (Even/Odd/None)
Possible settings: "Even", "Odd" or "None".
Stop bit
1 (1/2)
Possible settings: 1 or 2.
Modbus TCP Port
502 (1...32767)
This menu bar is displayed if "Modbus TCP" is defined
in the "Ethernet" row in the "Installer / Define / Remote
Control /" menu.
Menu: "Installer / Settings / Communication / Internet".
Menu: "Installer / Settings / Communication / BMS".