background image

CTA  

Instruction Manual  

MPE  

Reference:  MT0027DA  

This document may be modified without prior notice 

6

 

Revision date: 11/05/06 

Even partial reproduction is prohibited without authorisation in writing 

 

3

 

Installation  

The installation procedures described in this chapter must only be executed by qualified personnel. 

The following procedure must be scrupulously respected or the safety of all staff could be at risk.   

3.1

 

Inspection  

Immediately after unpacking the drier, check that it is undamaged.  If necessary, make a damage claim to 
the carrier who delivered the equipment.  

 

Never install or use an appliance damaged during shipment.  

3.2

 

Handling  

If using hoists to lift the equipment make sure they are safe. To prevent accidents, check that all chains, hooks, 
rings, slings, etc., are in good condition and suitable for the load.  They must be tested and approved as 
stipulated in local safety regulations. Cables, chains and ropes should never be attached directly to the lift 
lugs. Always use a correctly positioned ring or a hook.  Lay out the lift so that hoisting cables do not form 
excessively tight curves.  

Use a bar to avoid side loads on hooks and lugs.  Stand at a safe distance away from the load while it is being 
lifted. Ensure that lift accelerations and velocities are within safety limits and never leave a load suspended 
longer than necessary.   

3.3

 

Layout  

Throughout installation, stop compressed air production of to avoid risks to installation personnel.  

1.

 

The dryer should be installed on a flat surface 
suitable for the weight of the appliance in a 
closed, dry, room which cannot freeze. Access 
to the room must be restricted to qualified 
maintenance and test personnel.  The room 
must be sufficiently ventilated with clean air free 
from flammable gases or solvents.  The drier must 
not be exposed directly to heat sources.  The 
temperature of the room must not exceed 43C°.   

Minimum and maximum ambient temperatures are 

specified on the manufacturer's plate on the 
drier.  Unless otherwise stated, dryers are 
designed to function in ambient conditions at a 
temperature of 25C°. Higher temperatures may 
reduce the capacity of the drier and result in an 
increase in the dew point.  Usually this does not 
cause a problem if the compressed air network is 
also in higher ambient temperature conditions.  

2.

 

Check that the drier is not surrounded by 
equipment which does not comply with 
European electromagnetic compatibility 
directives as interference could deteriorate 
appliance operation. Leave a minimum 1 m 
space between the drier and all other electrical 
appliances.  

3.

 

Leave adequate space around the drier for 
maintenance. Position the drier to ensure that 
cooling air cannot recirculate towards the 
suction ports. Check that the drier does not suck 

in hot air from the compressor cooling systems, 
the final cooler or any other appliance.  

Remark: The cooling air used by the dryer comes in by the rear 

grid and comes out by the front grid 

4.

 

The position of the drier in the compressed air 
distribution system depends on the way the 
compressed air will be used (see installation 
plan).  

 

The drier must be installed downstream  from  the tank if the 
compressor pumps intermittently or if total demand for air 

does not exceed the total compressor flow rate capacity (the 

usual case).  

 

The drier should be installed upstream from the tank if the tank 
has been dimensioned to permit wide fluctuations in 

compressed air demand or if peak demand exceeds 

maximum compressor flow rate capacity.  

5.

 

Fit by-pass valves between the drier inlet and 
exhaust so that maintenance can be carried 
out without having to shut down the 
compressed air supply to the network (see 
diagram below).  During installation, the 
upstream and downstream valves must be 
closed. 

6.

 

Additional fittings  
- fit a class 4* type solid pollutants filter (15m, 
µ8mg/m3) upstream from the drier  
- fit a class 1* type total oil 1filter  (0.01mg/m3) 
downstream from the drier to remove dust and 
oil from the compressed air. Only use filters 

equipped with an automatic purge system.    

 

 

 

Summary of Contents for MASTERIA MPE 004

Page 1: ...of the Air ZA du caillou 3 rue Jules Verne 69630 CHAPONOST FRANCE Phone 33 0 4 78 56 70 70 Fax 33 0 4 78 56 17 31 Instruction Manual MASTERIA compressed air dryer INSTALLATION USE MAINTENANCE Models...

Page 2: ...ce 9 5 2 Changing set points 9 5 3 Changing purging duration 10 5 4 Purge test 10 5 5 Choice temperature unit 11 6 Maintenance preparation 11 6 1 Shut down and close all circuits 11 6 2 Access inside...

Page 3: ...due to an air to air heat exchanger in all models in the range above the MPE010 The dry cold air from the drier is used to pre cool the hot wet air inlet Mechanical separation guaranteed in all opera...

Page 4: ...s install manual valves so each machine can be isolated separately Fit a safety valve to each tank or appliance containing air at a pressure higher than atmospheric pressure Fit a safety valve between...

Page 5: ...PROGRESS DO NOT ENERGISE warning panel Do not touch the master switch and do not try to start the drier if the warning panel is in place 3 Close the by pass valves up and down stream from the drier an...

Page 6: ...ratures are specified on the manufacturer s plate on the drier Unless otherwise stated dryers are designed to function in ambient conditions at a temperature of 25C Higher temperatures may reduce the...

Page 7: ...or treatment see ISO standard 8573 1 For air dryer inlet and outlet connexion s tightening be sure not to use too much screwing tight power which would damage the evaporator coil piping of the thermal...

Page 8: ...inutes and will only start again when the digital display panel indicates 04 C or 39 F If the compressed air flow oscillates it is normal for these values to be exceeded temporarily 10 Check that the...

Page 9: ...unit s electronic regulation LEDs 4 LEDs indicate the operating condition of the drier or the regulation 5 2 Changing set points General The factory programmed set point normally meets the nominal ca...

Page 10: ...on value flashes on the digital display panel Use the buttons to modify the purging duration value The adjustment range is from 1 to 10 seconds To record the new value wait 5 seconds without pressing...

Page 11: ...liance OFF as stipulated in 4 1 Lock the power supply cut out switches OPEN Lock the upstream and downstream valves CLOSED and the by pass valve OPEN Check that the appliance is depressurised by press...

Page 12: ...variation in pressure could damage the drier 3 Slowly open the upstream valve 4 Slowly close the by pass valve 7 Maintenance operation Various risks electrocution explosion The following operations m...

Page 13: ...to the solenoid purge valve 10 Open the manual valve on the purging line You must comply with the recommendations at the beginning of this chapter 8 Test and maintenance scheduling Frequency of interv...

Page 14: ...er 9 Alarm When temperature sensor is broken or short circuited the first digit point see diagram 5 1 will blink and the display show value 00 In the same time the compressor of the drier cut off Repl...

Page 15: ...low through the drier The condensates have frozen and block the passage as the probe is incorrectly positioned Compressed air does not flow through the drier Position the probe in the centre of the DT...

Page 16: ...a high evaporation pressure of raised and higher purging from the separator Correct the temperature and the air flow to pre set limits Press the red button on the Pressure switch cap F Low pressure L...

Page 17: ...5 1 1 1 3 1 5 1 85 2 2 2 4 2 8 3 2 3 50 Refrigerant Fluid R134a R407c Load gr see on the data sticker at the back panel HP Pressure switch bar 18 26 Manual Reset LP pressure controller bar 1 automatic...

Page 18: ...the operations described in 4 3 and 4 4 must be carried out Your Mast ria drier is pre fitted for an external purge with a level detection system To connect this type of purge you must 1 Raise your d...

Page 19: ...4A Label Components 006 020 025 125 AO Compressed air exhaust AI Compressed air inlet CD Condensing unit CF Condensate filter CO Condensate discharge CP Compressor CS Condensate separator CT Capillary...

Page 20: ...ng 14 2 Wiring diagrams SE00148 SE0015 SE0018 SE0017 and SE0018 Label Components M1 Compressor M2 Fan motor EC Electronic card EV Solenoid purge valve HPS High pressure switch LPS Low pressure switch...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Reviews: