EZT-570i Technical Manual
79
redundant operation is specified, the EZT-570i will display the readings from the
operating plenum. If tandem operation is specified, the EZT-570i will display the
average reading from both plenum control loops.
Refrig Cycle Time
The refrigeration cycle time sets the interval period used for redundant refrigeration in which the EZT-
570i will alternate between systems to equalize run time.
Refrig Overlap Time
The refrigeration overlap period sets the time period for redundant refrigeration in which the systems
will overlap to allow the system that is just starting enough time to get to operating temperature.
Typically required for cascade systems to allow the stager start delay period to expire prior to turning
off the currently operating system.
Floodback Alm Band
The floodback alarm band is used for Tundra II systems to set the mnimum superheat allowed at the
suction of the compressor to prevent liquid floodback from damaging the compressor. The “Tundra
Floodback Alarm” must be enabled for this setting to be used. When enabled, and the superheat falls
below this setting, the maximum cool output is disabled and the alarm delay is activated.
Floodback Alm Dly
The floodback alarm delay is used for Tundra II systems to set the alarm delay period when a
floodback condition is detected based on the superheat falling below the floodback alarm band
setting. The “Tundra Floodback Alarm” must be enabled for this setting to be used.
Tundra Floodback Alarm Enable/Disable
The Tundra floodback alarm is used for Tundra II systems to detect a floodback condition at the
compressor which could lead to compressor damage due to liquid slugging. When enabled, logic in
the EZT-570i will be activated and use a 9300 controller to monitor the suction temperature and
pressure at the compressor and shut down the system if a floodback condition is detected.
Summary of Contents for EZT-570i
Page 1: ...EZT570i Technical Manual Rev B EZT 570i Technical Manual...
Page 14: ...EZT 570i Technical Manual 14 4 1 6 Conditioning System Logic Flow...
Page 15: ...EZT 570i Technical Manual 15...
Page 19: ...EZT 570i Technical Manual 19 4 2 2 Humidity System Logic Flow...
Page 21: ...EZT 570i Technical Manual 21 4 3 2 Auxiliary Cooling System Logic Flow...
Page 23: ...EZT 570i Technical Manual 23 4 4 2 Dry Air Purge System Logic Flow...
Page 25: ...EZT 570i Technical Manual 25 4 5 2 Altitude System Logic Flow...
Page 29: ...EZT 570i Technical Manual 29 4 7 2 Transfer System Logic Flow...
Page 30: ...EZT 570i Technical Manual 30...
Page 58: ...EZT 570i Technical Manual 58 7 2 Standard Output Configuration...
Page 92: ......