CSZ EZT-570i Technical Manual Download Page 55

EZT-570i Technical Manual

 

 

 

 

55 

 
System 1B Pumpdown Switch (I31): 

This input is a control input for pumpdown (if equipped).  There is 
no user indication for this input.  When refrigeration system 
requires pumpdown, this input is wired to a low pressure switch 
on the suction line of system 1B compressor.  When the 
pressure rises, the switch closes and turns on the input. 
 
The EZT then turns on the system 1B compressor output (Q46) 
until the input turns off.  When the input turns off, indicating that 
the compressor has pumped down, the EZT turns off the system 
1B compressor output.  During pumpdown, the system 1B 
solenoids output (Q45) remains off in order to isolate the low 
side of the refrigeration system so it can be pumped down. 

 
 
Sys ‘A’ Oil Pressure Safety (I33): 

The system ‘A’ oil pressure safety input is used to indicate that 
the system 1A or system 2A compressor oil pressure is below 
the proper operating range (if equipped).  This input is active low, 
i.e., the input must be off in order for the alarm to be indicated.  
When active (input off), the EZT shuts down the chamber until 
the alarm is acknowledged (silence button pressed on alarm 
monitor screen) and the input is on (requires manual reset of oil 
pressure safety). 

 
Sys ‘A’ Protection Module (I34): 

The system ‘A’ compressor protection module input is used to 
indicate that the system 1A or system 2A compressor protection 
module has detected an improper phase condition/loss or the 
compressor motor windings have overheated (if equipped).  This 
input is active low, i.e., the input must be off in order for the 
alarm to be indicated.  When active (input off), the EZT shuts 
down the chamber until the alarm is acknowledged (silence 
button pressed on alarm monitor screen) and the input is on 
(automatically resets after built-in timeout period). 

 

Sys ‘B’ Discharge Thermostat (I35): 

The system ‘B’ discharge thermostat input is used to indicate 
that the system 1B or system 2B compressor discharge 
temperature has exceeded the maximum operating range (if 
equipped).  This input is active low, i.e., the input must be off in 
order for the alarm to be indicated.  When active (input off), the 
EZT shuts down the chamber until the alarm is acknowledged 
(silence button pressed on alarm monitor screen) and the input is 
on (automatically resets after allowed to cool down). 

 
Sys ‘B’ Oil Pressure Safety (I36): 

The system ‘B’ oil pressure safety input is used to indicate that 
the system 1B or system 2B compressor oil pressure is below 
the proper operating range (if equipped).  This input is active low, 
i.e., the input must be off in order for the alarm to be indicated.  
When active (input off), the EZT shuts down the chamber until 
the alarm is acknowledged (silence button pressed on alarm 
monitor screen) and the input is on (requires manual reset of oil 
pressure safety). 

 
 
 
 
 

Summary of Contents for EZT-570i

Page 1: ...EZT570i Technical Manual Rev B EZT 570i Technical Manual...

Page 2: ...4 Dry Air Purge System 22 4 4 1 Dry Air Purge System Failures and Corrective Actions 22 4 4 2 Dry Air Purge System Logic Flow 23 4 5 Altitude System 24 4 5 1 Altitude System Failures and Corrective A...

Page 3: ...em Redundant Refrigeration 65 7 3 Control Module Status Indicators 67 8 Adjusting EZT Configuration options 68 8 1 Accessing the EZT Configurator 68 8 2 Number of Loops Monitors 71 8 3 Loops Monitor T...

Page 4: ...nce A WARNING safety alert appears with information that is important for protecting you others and equipment from damage Pay very close attention to all warnings that apply to your chamber 1 2 How to...

Page 5: ...g for the heater Is there voltage to the heaters Is the heat output of the controller on i e is the solid state relay on to supply power to the heater Is the heater contactor on Is there a blown fuse...

Page 6: ...tart due to a communications failure or other hardware problems Section 7 Deciphering EZT Input Output I O Operation This section reviews the functionality of the inputs and outputs of the EZT and how...

Page 7: ...ated humidity sensor the humidity setpoint entered may not match that on the 9300 controller depending upon the current air temperature reading This is due to the temperature compensation algorithm in...

Page 8: ...at may occur during operation Section 4 3 Auxiliary Cooling System This section covers typical problems that may arise with the chamber s auxiliary cooling system It includes information regarding the...

Page 9: ...re heaters and their surface is not electrically live This allows a temperature sensor typically a thermocouple to be placed on their surface The sensor is then connected to a limit device This limit...

Page 10: ...ines how system 1 is controlled in order to cool system 2 With standard defrost the system 1 compressor is cycled on and off based on system 2 head pressure With large horsepower defrost system 1 comp...

Page 11: ...dditional inputs and outputs are used to start and stop the air circulators on plenum B Q44 as well as monitor for heater over temperature I4 motor overload I5 and a second boiler system on the additi...

Page 12: ...defrost if equipped Turn on chamber event Altitude above controllable limit for temperature Decrease altitude or turn off altitude system Replace fuse Check heater limit Maximum temperature reached Ve...

Page 13: ...r in defrost if equipped Refrigeration system capacity exceeded Turn on chamber event Altitude above controllable limit for temperature Decrease altitude or turn off altitude system Initiate defrost o...

Page 14: ...EZT 570i Technical Manual 14 4 1 6 Conditioning System Logic Flow...

Page 15: ...EZT 570i Technical Manual 15...

Page 16: ...for the system B refrigeration system is the same as that shown in the chart above for a standard chamber with a single refrigeration system The logic is merely duplicated and tied to different output...

Page 17: ...r The humidity system will restart automatically once the air temperature returns to within the set temperature range Dewpoint Limits In order to protect the refrigeration system and chamber from dama...

Page 18: ...d Atomizer water supply low Atomizer air supply low Check system status monitor Chamber operating at maximum humidity level Check water supply Allow time for boiler to heat up Replace fuse Verify prop...

Page 19: ...EZT 570i Technical Manual 19 4 2 2 Humidity System Logic Flow...

Page 20: ...Cool Control Operation When auxiliary cooling is set for control in the configurator the auxiliary cooling system will operate according to the boost control logic until the low limit set point is rea...

Page 21: ...EZT 570i Technical Manual 21 4 3 2 Auxiliary Cooling System Logic Flow...

Page 22: ...oints and calculates the resulting dewpoint When this value is below the standard wet coil range the EZT will automatically switch to frozen coil mode The EZT does not initiate frozen coil mode until...

Page 23: ...EZT 570i Technical Manual 23 4 4 2 Dry Air Purge System Logic Flow...

Page 24: ...ooling is shut down During the allowed operating range the air circulator motors will switch from low speed output Q2 to high speed output Q44 once the high speed fan enable set point is reached This...

Page 25: ...EZT 570i Technical Manual 25 4 5 2 Altitude System Logic Flow...

Page 26: ...nd cooled as it flows across the heater and heat exchanger much like the air across the heater and evaporator in a typical chamber For TSB s with fluid pumps the fluid system is equipped with safeties...

Page 27: ...w or no fluid flow Blockage in piping closed valves Pressure relief valve bypassing fluid Pump failure Blown fuse Locate blockage and remove open valves Check pump pressure Adjust replace relief valve...

Page 28: ...nues to push on the basket thus sealing the gasket surface to keep the hot and cold chambers separate Limit switches are positioned on each end of the cylinder in order to identify the basket position...

Page 29: ...EZT 570i Technical Manual 29 4 7 2 Transfer System Logic Flow...

Page 30: ...EZT 570i Technical Manual 30...

Page 31: ...e 5 1 Web Server Modbus VNC Communication Settings For more detailed information on communication format commands and functionality of the 232 485 serial interfaces see the EZT 570i User Communication...

Page 32: ...t with a default address of 1 and Even parity Even parity is required when using CSZ EZ View software to communicate with the EZT The baud rate data bits and stop bits of the serial interface are fixe...

Page 33: ...also have its parity set to Even in order for EZ View to communicate with it Controllers must be enabled in order If a controller is skipped it will not cause a direct communication error however the...

Page 34: ...able to take place Table 5 3 Common GPIB Communication Problems and Corrective Actions SYMPTOM PROBABLE CAUSES CORRECTIVE ACTIONS GPIB interface not responding to read write commands 4899 power turned...

Page 35: ...server To use either interface you must use the assigned IP address to access the EZT 570i To obtain the correct IP address go to the Web Server Modbus VNC screen under the chamber setup menu Enter th...

Page 36: ...information gathering and monitoring of chamber operations only The information is exchanged over an RS232 serial communication link between the HMI and the EZT 570i s control module CM mounted on th...

Page 37: ...lication not starting SD card missing improperly inserted or erased Windows CE startup directory not properly configured Verify SD card is inserted properly Check SD card for EZT570i operating files C...

Page 38: ...C minimum 500ms scan rate 4 Screen Locked Up Screen does not respond to touch Touch screen out of calibration VNC server not properly disconnected after previous access via remote PC HMI operating tem...

Page 39: ...files however we are only concerned with the Startup folder If the startup folder does not exist then it must be created If the startup folder does exist open the folder and make sure there is a shor...

Page 40: ...on the splash screen The hour glass will continue to turn and the COM LED on the HMI will flash as it tries to communicate with the CM Figure 6 3 Write Error on Boot To check the serial port settings...

Page 41: ...mmunications and its mode does not affect the communications between the HMI and control module Figure 6 6 Serial Port Settings Set the serial port mode for COM1 to RS232 by touching the radio button...

Page 42: ...switch 1 to the on up position Restore power to the EZT Allow the HMI to follow its normal boot sequence Once the Windows CE image is loaded the display will automatically start the touch screen cali...

Page 43: ...like using a desktop PC Begin by selecting Chamber Setup from the main setup menu Figure 6 8 Setup Menu Access Select System Maintenance from the setup menu Figure 6 9 Chamber Setup Menu Access You w...

Page 44: ...ance Setup menu Access Press the Yes button to proceed to the CECP utility Figure 6 11 Calibrate Touch Press the Touch Screen icon on the CECP settings screen and then press Calibrate to start the cal...

Page 45: ...where on the screen to accept the settings and complete the calibration routine Do not use any metal or sharp edged instruments on the screen or permanent damage to the screen may result Figure 6 13 T...

Page 46: ...CHAMBER HOT CHAMBER BATH ON LEFT CHAMBER 2 HUMIDITY COLD CHAMBER CENTER CHAMBER 3 AUX COOL AUX COOL AUX COOL 4 PURGE PURGE PURGE 5 ALTITUDE XFR HOT XFR LEFT 6 XFR COLD XFR RIGHT 7 XFR UNLOAD RIGHT CH...

Page 47: ...Technical Manual 47 7 1 Standard Input Configuration Dual Refrigeration refers to a refrigeration type selection of tandem or redundant meaning there are two duplicate refrigeration systems cooling th...

Page 48: ...larm is acknowledged silence button pressed on alarm monitor screen and the input is no longer active requires manual reset of motor overload It may also be used to indicate a failure of a VFD if one...

Page 49: ...ven sufficient time to fill 30 minute delay upon turning on the humidity event If the boiler has not filled up in the allotted time the alarm will sound Once the boiler has reached the proper operatin...

Page 50: ...equipped This input is active low i e the input must be off in order for the alarm to be indicated When active input off the EZT shuts down the chamber until the alarm is acknowledged silence button p...

Page 51: ...ignaling that the coil defrost temperature has been met When the input first turns on the EZT will begin the 15 minute countdown to terminate defrost The thermostat is typically set for about 10 C 50...

Page 52: ...cknowledged silence button pressed on alarm monitor screen and the input is off Fluid Flow Safety I46 The fluid system flow safety input is used to indicate that the fluid system has proper flow LC ch...

Page 53: ...wn position There is no user indication for this input TSB Pump Pressure Safety I45 The pump pressure safety input is used on TSB s to indicate that the hot or cold bath fluid pump has exceeded its ma...

Page 54: ...The system B hi lo pressure safety input is used to indicate that the system 1B or system 2B compressor has exceeded its high or low pressure operating range This input is active low i e the input mu...

Page 55: ...ut is used to indicate that the system 1A or system 2A compressor protection module has detected an improper phase condition loss or the compressor motor windings have overheated if equipped This inpu...

Page 56: ...a 60 second prechill timer will begin At the end of 60 seconds the chamber will return to normal operation If the control loop is not calling for 100 cooling the prechill timer will begin its 60 secon...

Page 57: ...a boiler on each plenum Thus this input is used to indicate that the boiler on plenum B has overheated This input is active low i e the input must be off in order for the alarm to be indicated When a...

Page 58: ...EZT 570i Technical Manual 58 7 2 Standard Output Configuration...

Page 59: ...utput also turns on and off with the pressure switch input I32 if pumpdown is enabled If main power is off for more than 30 minutes the input will be ignored and the output will remain off until pumpd...

Page 60: ...can be pumped down During normal cooling operation this output will turn on with the system 1 compressor output Q3 When the refrigeration system is no longer required to run this output will turn off...

Page 61: ...ay time set in the configurator Rate Master Control Q40 This output is used for rate master refrigeration systems It is used to switch cooling control between the system 1 and system 2 valves When the...

Page 62: ...and is used to turn the RC blower on and off when the chamber is on and event 8 is turned on and off If defrost is enabled this output will turn off the blower during defrost and will turn it back on...

Page 63: ...t Hi Speed Fan Enable SP in the configurator this output turns on When the altitude drops below the set point this output turns back off so the low speed fan output Q2 can turn on and control the air...

Page 64: ...the door from being opened during a transfer When the transfer is complete the output turns off Transfer Left Q32 This output is used to turn on the transfer mechanism to move the basket to the left o...

Page 65: ...ystem 1B when the unit is equipped with pumpdown This allows the solenoids to open and close independently of system 1B compressor operation so that the system can be pumped down During normal cooling...

Page 66: ...The output turns off when system 1B output turns off During single stage humidity operation the output is also turned off The output will remain off until humidity is turned off The stager start time...

Page 67: ...hat means that the inputs and outputs increment in groups of 8 and are assigned sequentially as the input and output cards are added The first group of inputs is I0 I7 on the CPU while outputs are Q0...

Page 68: ...e EZT Configurator To access the EZT configurator you must quit the EZT570i application and start the configurator program To do this you must have the proper security access to exit the EZT applicati...

Page 69: ...dows CE desktop blue screen Insert the SD card back into the slot in the HMI making sure to insert it in the proper orientation Touch the thin gray bar at the bottom of the screen to show the Windows...

Page 70: ...Figure 8 4 EZT570i Folder Select EZT570i Config from the EZT570i folder to start the configurator program Figure 8 5 EZT570i Config When the configurator application starts it will default to the Num...

Page 71: ...op is selected and enabled disabled If a loop is being removed you must first change the loop to disabled and then change the total number of control loops Only changing the number of control loops wi...

Page 72: ...f control loop temperature humidity altitude etc Do not alter the loop type to any selection other than what is called out on the EZT Configuration form supplied with the chamber or the chamber may no...

Page 73: ...will turn on The EZT automatically assigns the digital outputs of additional relays cards for specific options as enabled in the configurator For a standard dry chamber non humidity that does not hav...

Page 74: ...or the pump with event 1 and enables the input alarm logic for high temperature I44 pressure I45 and flow I46 monitoring VTS Logic Enabled Enables the logic for basket position and dual zone control L...

Page 75: ...and Q47 used to control the up and down movement Events 5 hot and 6 cold with event 7 for the unload position are used to select the three positions Inputs I6 and I7 are used to monitor the left hot...

Page 76: ...ase selections include Single Stage selection for standard single stage systems typically R404a Tundra selection for single stage systems using R410a Cascade selection for standard cascade systems Rat...

Page 77: ...rost On is used for smaller compressors typically smaller than 7 5hp Large HP Defrost is used for larger systems typically larger than 7 5hp The large horsepower defrost is used to control the cascade...

Page 78: ...ation system will only operate in cascade mode For Tundra systems this setpoint defines the chamber air temperature below which the maximum cool output of the EZT is disabled Refrig Settings These but...

Page 79: ...undra II systems to set the mnimum superheat allowed at the suction of the compressor to prevent liquid floodback from damaging the compressor The Tundra Floodback Alarm must be enabled for this setti...

Page 80: ...e systems that run in single stage mode during humidity have separate RH cooling circuit on system 1 Cmp On Sets the loop percentage of output required to enable the refrigeration system in order to p...

Page 81: ...algorithm in the EZT depending on whether or not a compensated sensor is used The compensation is for a Vaisala HMM30C sensor only Do not use it for other brands of sensors This should be disabled whe...

Page 82: ...frozen coil option is installed Min Dewpoint Limit Sets the minimum dewpoint that the chamber will control to In essence this limits the minimum humidity level that the chamber can achieve at a given...

Page 83: ...ature operation which go colder than the range of the refrigeration system Boost Cool Temp SP Disable Sets the temperature below which the refrigeration system is automatically disabled if aux cool co...

Page 84: ...ble buttons Parameter Descriptions Window Heater Enable SP Sets the temperature below which the window heater turns on Alt Hi Speed Fan Enable SP Sets the altitude in Kft above which the high speed fa...

Page 85: ...Figure 8 15 CSZ Event Names To change or edit a tag name touch the position for the event and change the name using the pop up keypad Note that event names are limited to 20 characters in length Alter...

Page 86: ...he chamber Figure 8 16 Critical Chamber Alarm Names To change or edit a tag name touch the position for the alarm and change the name using the pop up keypad Note that alarm names are limited to 20 ch...

Page 87: ...tem alarms Figure 8 17 Critical Refrigeration Alarm Names To change or edit a tag name touch the position for the alarm and change the name using the pop up keypad Note that alarm names are limited to...

Page 88: ...rvice monitors Figure 8 18 Non Critical Alarm Names To change or edit a tag name touch the position for the alarm and change the name using the pop up keypad Note that alarm names are limited to 20 ch...

Page 89: ...m component Figure 8 19 Maintenance Alarm Names To change or edit a tag name touch the position for the alarm and change the name using the pop up keypad Note that alarm names are limited to 20 charac...

Page 90: ...plication Figure 8 20 Special Settings Names To change or edit a tag name touch the position for the alarm and change the name using the pop up keypad Note that alarm names are limited to 10 character...

Page 91: ...ou must rotate the small pot on the control module CPU Figure 8 21 EEPROM Configuration Back up Gently turn the pot full counterclockwise then fully clockwise and back counterclockwise again The small...

Page 92: ......

Page 93: ...EZT 570i Technical Manual 1 Appendix...

Page 94: ...ion Screen 45 Figure 7 1 Control Module Input Output Indicators 67 Figure 8 1 Exit Application 68 Figure 8 2 Windows Start Menu 69 Figure 8 3 Storage Card 69 Figure 8 4 EZT570i Folder 70 Figure 8 5 EZ...

Page 95: ...Corrective Actions 32 Table 5 2 Common EZ View Start up Problems and Corrective Actions 33 Table 5 3 Common GPIB Communication Problems and Corrective Actions 34 Table 5 4 Common Ethernet Communicati...

Reviews: