19
FIGURE 8.1: STANDARD BOILER PIPING
Standard Piping
Figure 8.1 shows typical boiler system connections on a single zone system. Additional information on hydronic system
design may be found in the
I=B=R
Guide RHH published by the Air-Conditioning, Heating and Refrigeration Institute
(AHRI). The components in this system and their purposes are as follows:
VIII System Piping
WARNING
• Install boiler so that the electrical components are protected from water (dripping,
spraying, rain, etc.) during appliance operation and service (circulator replacement,
etc.).
• Operation of this boiler with continuous return temperatures below 120°F can cause
severe heat exchanger corrosion damage.
• Operation of this boiler in a system having significant amounts of dissolved oxygen can
cause severe heat exchanger corrosion damage.
• Do not use toxic additives, such as automotive antifreeze, in a hydronic system.
• Pipe relief valve discharge to a safe location. The relief valve may discharge scalding
hot water.
• Do not install a valve in the relief valve discharge line.
• Do not move relief valve from factory location.
• Do not plug relief valve discharge. Blocking the relief valve may result in boiler
explosion.
Summary of Contents for TWB Series
Page 2: ......
Page 12: ...10 FIGURE 4 1 FIELD INSTALLATION OF FLUE BAFFLES...
Page 18: ...16 FIGURE 6 4 ALLAIR FROM OUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM...
Page 23: ...21 FIGURE 8 3 BOILER BYPASS PIPING FIGURE 8 2 INDIRECT WATER HEATER BOILER SIDE PIPING...
Page 31: ...29 FIGURE 11 0 CONNECTIONS DIAGRAM BOILERS WITH OR LESS TANKLESS HEATER...
Page 51: ...49...
Page 53: ...51...
Page 54: ...52 SERVICE RECORD DATE SERVICE PERFORMED...
Page 55: ...53 Notes...