VII Venting
Vent installation must be in accordance with local building codes, or the local authority having jurisdiction.
Typical vent installation is illustrated by Figure 7.0. The components of vent installation are the vent connector (breeching),
barometric draft regulator, and chimney.
1) Acceptable Chimneys - The following chimneys may be used to vent this boiler:
•
Listed Type L vent - Install in accordance with the manufacturer’s instructions, the terms of its listing, and applicable
codes.
•
Masonry Chimney - The masonry chimney must be constructed in accordance with the latest edition of
Standard
for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances
(NFPA 211) and lined with a clay liner or other
listed lining system. Do not vent this boiler into an unlined chimney
.
FIGURE 7.0: TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS
WARNING
• Improper venting may result in property damage and/or the release of flue gases, which
contain deadly carbon monoxide (CO), into the home, resulting in severe personal injury or
death.
• Inspect existing chimney before installing boiler. Failure to clean or replace damaged pipe
or tile lining will cause property damage, severe personal injury or death.
Summary of Contents for TWB Series
Page 2: ......
Page 12: ...10 FIGURE 4 1 FIELD INSTALLATION OF FLUE BAFFLES...
Page 18: ...16 FIGURE 6 4 ALLAIR FROM OUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM...
Page 23: ...21 FIGURE 8 3 BOILER BYPASS PIPING FIGURE 8 2 INDIRECT WATER HEATER BOILER SIDE PIPING...
Page 31: ...29 FIGURE 11 0 CONNECTIONS DIAGRAM BOILERS WITH OR LESS TANKLESS HEATER...
Page 51: ...49...
Page 53: ...51...
Page 54: ...52 SERVICE RECORD DATE SERVICE PERFORMED...
Page 55: ...53 Notes...