24
FIGURE 9.1: TANKLESS HEATER PIPING
X Fuel Line Piping
Fuel line piping design, materials and construction must be in accordance with local building codes, requirements of the lo
-
cal authority having jurisdiction, and, the latest edition of the Standard for the Installation of Oil-Burning Equipment (ANSI/
NFPA 31) in the United States and CSA B139-04 for installation in Canada. Refer also to the instruction manuals provided
with the burner.
WARNING
• Under no circumstances can copper with sweat style connectors be used.
• Do not use compression fittings.
• Oil piping must be absolutely airtight or leaks or loss of prime may result.
• Some jurisdictions require the use of a fusible shutoff valve at the tank and/or the burner.
in addition, some jurisdictions require the use of a fusible electrical interlock with the
burner circuit. Check your local codes for special requirements.
Summary of Contents for TWB Series
Page 2: ......
Page 12: ...10 FIGURE 4 1 FIELD INSTALLATION OF FLUE BAFFLES...
Page 18: ...16 FIGURE 6 4 ALLAIR FROM OUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM...
Page 23: ...21 FIGURE 8 3 BOILER BYPASS PIPING FIGURE 8 2 INDIRECT WATER HEATER BOILER SIDE PIPING...
Page 31: ...29 FIGURE 11 0 CONNECTIONS DIAGRAM BOILERS WITH OR LESS TANKLESS HEATER...
Page 51: ...49...
Page 53: ...51...
Page 54: ...52 SERVICE RECORD DATE SERVICE PERFORMED...
Page 55: ...53 Notes...