Sequence of Operation - Steam Boiler

1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damp-

er. Assuming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close. 

On boilers equipped with Hydrolevel CG400A probe type low water cut-offs, voltage  is also always applied to terminals 

“1” (blue) and “2” (yellow) on the low water cut-off to power the water level sensing circuit.

 

2) Assuming that water is above the cut-off level, power will appear at terminal “3” on the CG400 LWCO or terminal “1”. 

 

3) Assuming that steam pressure is below the pressure limit setting, power will appear on one side of relay contact 1R1 

(Gray lead). Relay 1R is the R8225 mounted under the junction box.

   

4) A call for heat from the thermostat energizes relay coil 1R causing contacts 1R1 to make. Current then flows through con-

tacts 1R1 to pin terminal “2” (orange) at the vent damper (if used) and the damper opens.

5) Once the vent damper is fully open, an end switch inside the damper will make, energizing pin “3” (red) at the damper. 

If a vent damper is not present, current flows through the red jumper indicated by Note 2 in Figure A directly to the blocked 

vent switch.

 

6) Current passes from terminal “3” on the vent damper through the blocked vent switch. Under normal conditions, this 

switch is made and voltage will therefore immediately appear across terminals “24V” and “24V (GND)” on the ignition 

module.

7) Upon application of voltage across the “24V” and “24V (GND)” terminals, the ignition module will start an ignition 

spark at the pilot and apply 24 volts across the pilot valve (terminals “PV” and “MV/PV”).

 

8) Once the pilot is established, the pilot flame will act as a diode, converting the AC current at the electrode to a half wave 

DC current at the pilot’s ground strap. This DC current flows through the boiler to the “GND (BURNER)” connection on 

the ignition module. For the ignition module to recognize that a pilot flame is present, the DC current flowing into this ter-

minal must be in excess of approximately 1.0 uA. 

9) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve (terminals “MV” 

and “MV/PV”), opening the valve and establishing main flame.

 

10) The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot 

depends upon the exact ignition module supplied with the boiler. For more information on module operation, consult the 

ignition module instructions supplied with the boiler or the local Crown representative.

Safety Control Operation - Steam Boilers

 

Hydrolevel CG400A Low Water Cut-off - Interrupts burner operation if the water in the boiler drops below a safe level. 

As the water drops past the cut-off point, the amber lamp on the CG400 will glow. The CG400 will interrupt power to the 

burners 15 seconds after the water level drops past the cut-off point. This feature prevents short cycling of the burners due 

to a bouncing water line. The burners will then remain off until 30 seconds after the water level has been raised above the 

cut-off point. 

   The CG400 is also equipped with a feature which will shut down the burners after they have been firing for 20 minutes, 

regardless of the water level status. The CG400 then keeps the burners off for 90 seconds, allowing the water level and any 

foam which is present to settle. During this 90 second interval, the green LED on the CG400 will glow. If the water level is 

still above the cut-off line at the end of this 90 second interval, the CG400 will restart the burners.

   The vent damper will close when the low water cut-off interrupts burner operation.

Pressure Limit Control - Interrupts burner operation when the pressure in the boiler exceeds the “Cut-in”  setting plus the 

differential setting. The “Cut-in” setting is shown on the outside of the control and is adjusted using the screw on the top 

of the control. The differential is adjusted using the white thumb wheel on the inside of the control. Burner operation is 

restored when the pressure in the boiler drops to the “Cut-in” pressure.

Blocked Vent Switch - Automatically interrupts burner operation in the event of a blocked vent condition. This switch is 

5

Summary of Contents for 32-380ECS

Page 1: ...ral Draft Steam or Water Boilers Installation SUPPLEMENT FOR 32 380ECS 32 475ECS EQUIPPED WITH 24 VOLT CONTROL SYSTEMS Warning Improper installation adjustment alteration service or maintenance can ca...

Page 2: ......

Page 3: ...R Net Rating MBH Steam 228 I B R Net Rating ft2 Steam 950 Combustion Effy 80 5 Steam Water Volume to Normal Water Line Gal 24 51 Water Boiler Volume Gal 34 13 Output BHP 9 1 Arrangement of Steam Rise...

Page 4: ...ng Figures D and F in the Wiring section show typical damper orientation 4 Install vent connector pipe and vent fittings from vent damper outlet to chimney or gas vent Secure with sheet metal screws a...

Page 5: ...e wiring in the junction box as shown in Figure A Route the damper harness to the damper as shown in Figure D using care to make sure that it does not come in contact with the draft hood or steam pipi...

Page 6: ...BLUE LEADS ARE JUMPED TOGETHER USING RED JUMPER WIRE RD RD RD ALARM ALARM 2 NOTE 2 2 WHEN DAMPER IS NOT USED DAMPER HARNESS IS REPLACED WITH JUMPER PLUG PILOT VALVE MAIN VALVE TH TR ROBERTSHAW 7000DER...

Page 7: ...into this ter minal must be in excess of approximately 1 0 uA 9 Once the ignition module detects the presence of a pilot flame voltage is applied across the main valve terminals MV and MV PV opening t...

Page 8: ...OW LIMIT HONEYWELL L8124E TH TR ROBERTSHAW 7000DERHC GAS VALVE PILOT VALVE MAIN VALVE RD RD RD YE RD RD YE ALARM ALARM Figure C Water Boiler Wiring With Tankless Heater Figure D Steam Boiler Control I...

Page 9: ...le to recognize that a pilot flame is present the DC current flowing into this ter minal must be in excess of approximately 1 0 uA 8 Once the ignition module detects the presence of a pilot flame volt...

Page 10: ...Figure F Water Boiler Control Installation Less Tankless Heater Version Shown Figure E Blocked Vent Switch Installation 8...

Page 11: ...allowable temperature is 250 F If the high limit opens the vent damper will close if the damper switch is in the automatic posi tion The circulator will continue to operate as long as there is a call...

Page 12: ...1063 1 REAR TIE ROD CHANNEL BRACKET 310311 1 1 5 8 X 4 STUD 900309 1 1 5 8 USS WASHER 900312 2 2 5 8 NUT 900311 2 2 JACKET REAR PANEL SUPPORT BRACKET 310310 1 1 JACKET TOP SUPPORT BRACKET 310320 1 1 1...

Page 13: ...X 7 8 HEX HD CAP SCREW 900450 12 10 X 1 2 SHEET METAL SCREW 90 212 5 NYLON CABLE CLAMP 960030 3 1 1 2 NPT BLK PLUG 95 143 2 1 NPT BLK PLUG 950100 2 3 4 NPT BLK PLUG 95 048 4 1 2 NPT BLK PLUG 95 052 7...

Page 14: ...E 95 070 1 1 2 X 1 4 BRASS BUSHING 95 146 2 1 2 X 3 BR NIPPLES 95 116 2 1 2 BR UNION 95 150 2 1 2 X CL BRASS NIPPLES 95 147 2 BLANK COIL PLATE 270003 2 COIL GASKET 270001 2 3 8 USS FLAT WASHER 90 036...

Page 15: ......

Page 16: ...PN 980895 05 10 Tel 215 535 8900 Fax 215 535 9736 www crownboiler com Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134...

Reviews: