WARNING

All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such 

CAUTION

Make sure that damper and BVS harnesses are secured so that they do not come in contact with draft hood or steam piping. 

XI Control System Wiring

Wire the boiler in accordance with the following instructions rather than those in the installation manual. Provide the boiler 

with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit must be 15A. Wire the boiler 

using the appropriate wiring diagram shown in Figures A-C in this supplement. In addition, note the following:

1) Steam boiler wiring is shown in Figure A. The junction box, transformer, and thermostat relay are prewired with all low 

voltage wire harnesses, except the damper harness (if used). 

a) Mount the junction box assembly to the side jacket panel as shown in Figure D using two #10 x 1/2” sheet metal 

screws. 

b) Connect the gray limit harness to terminals R and B on the L404 pressure limit.

c) Mount the blocked vent switch (BVS) to the draft hood as shown in Figure E using two #10 x 1/2” sheet metal 

screws. Route the red BVS harness along the side of the boiler as shown in Figure D and connect the pair of fully 

insulated quick connects to the BVS.   

d) Route the other end of the BVS harness to the ignition module . Connect the fully insulted quick connect to the 

“24 Volt” terminal. Connect the uninsulated connector to the “24 V Ground” piggy back terminal. Secure the BVS 

harness to the jacket with the nylon clips provided as shown in Figure D.  

e) If a damper is installed, remove the red jumper wire inside the junction box that is indicated by Note #2 in Figure A. 

Connect the damper harness to the wiring in the junction box as shown in Figure A. Route the damper harness to the 

damper as shown in Figure D, using care to make sure that it does not come in contact with the draft hood or steam 

piping. 

f) If a redundant LWCO and/or pressure limit are used, wire them so that they interrupt 120VAC power to the boiler.

 

2) Water Boiler wiring is shown in Figure B for boilers without a tankless heater and in Figure C for boilers with a tankless 

heater. The blocked vent switch (BVS) wire harness is factory wired to B1 and B2 on the “aquastat” (L8148E or L8124E).

  

a) Mount the aquastat to the control well.  

b) Mount the blocked vent switch (BVS) to the draft hood as shown in Figure E using two #10 x 1/2” sheet metal 

screws. Route the red BVS harness along the side of the boiler as shown in Figure F and connect the pair of fully 

insulated quick connects to the BVS.   

c) Route the other end of the BVS harness to the ignition module . Connect the fully insulated quick connect to the 

“24 Volt” terminal. Connect the uninsulated connector to the “24 V Ground” piggy back terminal. Secure the BVS 

harness to the jacket with the nylon clips provided as shown in Figure F.  

d) A vent damper cannot be used on boilers equipped with tankless heater.  If a damper is installed on a boiler without 

the tankless heater, remove the jumper plug inside the L8148E aquastat. Plug the 6-pole end of the damper harness 

into the aquastat. Plug the 4-pole end of the harness into the damper. Route the damper harness to the damper as 

shown in Figure F, using care to make sure that it does not come in contact with the draft hood. 

e) If a LWCO and/or redundant temperature limit are used, wire them so that they interrupt 120VAC power to the 

boiler. 

3) Provide a Class II circuit between the boiler and the thermostat. Make thermostat connections to the boiler in accordance 

with Figure A-C.

4) Make 120VAC connections to the boiler in accordance with Figure A-C. 

3

Summary of Contents for 32-380ECS

Page 1: ...ral Draft Steam or Water Boilers Installation SUPPLEMENT FOR 32 380ECS 32 475ECS EQUIPPED WITH 24 VOLT CONTROL SYSTEMS Warning Improper installation adjustment alteration service or maintenance can ca...

Page 2: ......

Page 3: ...R Net Rating MBH Steam 228 I B R Net Rating ft2 Steam 950 Combustion Effy 80 5 Steam Water Volume to Normal Water Line Gal 24 51 Water Boiler Volume Gal 34 13 Output BHP 9 1 Arrangement of Steam Rise...

Page 4: ...ng Figures D and F in the Wiring section show typical damper orientation 4 Install vent connector pipe and vent fittings from vent damper outlet to chimney or gas vent Secure with sheet metal screws a...

Page 5: ...e wiring in the junction box as shown in Figure A Route the damper harness to the damper as shown in Figure D using care to make sure that it does not come in contact with the draft hood or steam pipi...

Page 6: ...BLUE LEADS ARE JUMPED TOGETHER USING RED JUMPER WIRE RD RD RD ALARM ALARM 2 NOTE 2 2 WHEN DAMPER IS NOT USED DAMPER HARNESS IS REPLACED WITH JUMPER PLUG PILOT VALVE MAIN VALVE TH TR ROBERTSHAW 7000DER...

Page 7: ...into this ter minal must be in excess of approximately 1 0 uA 9 Once the ignition module detects the presence of a pilot flame voltage is applied across the main valve terminals MV and MV PV opening t...

Page 8: ...OW LIMIT HONEYWELL L8124E TH TR ROBERTSHAW 7000DERHC GAS VALVE PILOT VALVE MAIN VALVE RD RD RD YE RD RD YE ALARM ALARM Figure C Water Boiler Wiring With Tankless Heater Figure D Steam Boiler Control I...

Page 9: ...le to recognize that a pilot flame is present the DC current flowing into this ter minal must be in excess of approximately 1 0 uA 8 Once the ignition module detects the presence of a pilot flame volt...

Page 10: ...Figure F Water Boiler Control Installation Less Tankless Heater Version Shown Figure E Blocked Vent Switch Installation 8...

Page 11: ...allowable temperature is 250 F If the high limit opens the vent damper will close if the damper switch is in the automatic posi tion The circulator will continue to operate as long as there is a call...

Page 12: ...1063 1 REAR TIE ROD CHANNEL BRACKET 310311 1 1 5 8 X 4 STUD 900309 1 1 5 8 USS WASHER 900312 2 2 5 8 NUT 900311 2 2 JACKET REAR PANEL SUPPORT BRACKET 310310 1 1 JACKET TOP SUPPORT BRACKET 310320 1 1 1...

Page 13: ...X 7 8 HEX HD CAP SCREW 900450 12 10 X 1 2 SHEET METAL SCREW 90 212 5 NYLON CABLE CLAMP 960030 3 1 1 2 NPT BLK PLUG 95 143 2 1 NPT BLK PLUG 950100 2 3 4 NPT BLK PLUG 95 048 4 1 2 NPT BLK PLUG 95 052 7...

Page 14: ...E 95 070 1 1 2 X 1 4 BRASS BUSHING 95 146 2 1 2 X 3 BR NIPPLES 95 116 2 1 2 BR UNION 95 150 2 1 2 X CL BRASS NIPPLES 95 147 2 BLANK COIL PLATE 270003 2 COIL GASKET 270001 2 3 8 USS FLAT WASHER 90 036...

Page 15: ......

Page 16: ...PN 980895 05 10 Tel 215 535 8900 Fax 215 535 9736 www crownboiler com Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134...

Reviews: