8
Parameter
Default
Range / Option
Description
On Value
99
0 – 99
Dimmed output level when lights manually switched on or via detection of
occupancy.
Off Value
0
0 – 99
Dimmed output level when lights manually switched off or after detector
times out.
Burn-in Hours
0
1 – 999 hours
(0 = disabled)
Determines how long the output will be at 100% so that new lamps burn-in.
The burn-in time is not affected by power supply interruptions.
Speed (On)
40
0 – 99 seconds
Determines the dimming response speed during the set up time upon power
ON. Measured in 0.1 sec intervals.
If set to “0” will disable dimming for Set Seconds below, used if fittings are
required to warm up before dimming.
Speed (Setup)
5
0 – 99
Determines how long the dimming response set-up period lasts upon power-
up or on setting change. This enables a faster set up time.
Set Seconds
120
0 – 999 seconds
Sets the dimming response speed after the setup time has finished.
Measured in 0.1 sec intervals (i.e. a value of 40 means 4 seconds).
UNLCDHS Programming – Output Ch. 2
Advance Parameters available for EBDHS-B01-DD
UNLCDHS Programming – Device information
Under the device Info menu are items about the device that can be read back to the handset.
Note:
Not all devices support any or all of the information below.
• Range: e.g Standalone
• Part number: e.g MWS6
• Variant: e.g DD, PRM output variants
• Version: Version of software of the device.