PRESSURE SWITCHES FOR THE CONTROL OF CONDENSER FANS
(Only versions with controllers: Danfoss EKC331T / Carel IR32Z3 / Carel Micro Rack)
High pressure side
MT
LT
I.D. FUNCTION
R404A
bar (°C)
R404A
bar (°C)
START OF FAN #1
13,9
(+32,0)
13,9
(+32,0)
PV1
1
UTQ39080 -SHEET
8
DIFFERENTIAL 3,0
3,0
START OF FAN #2
15,0
(+35,0)
15,0
(+35,0)
PV2
UTQ39080 -SHEET
8
DIFFERENTIAL 3,0
3,0
START OF FAN #3
16,3
(+38,0)
16,3
(+38,0)
PV3
UTQ39080
SHEET 8
DIFFERENTIAL 3,0
3,0
START OF FAN #4
17.0
(+40,0)
17.0
(+40,0)
PV4
UTQ39080 -SHEET
8
DIFFERENTIAL 3,0
3,0
PRESSURE-SWITCH FOR THE CONTROL OF CONDENSER FANS WHEN UNDER
BACK-UP FUNCTIONING
(Only versions with controllers: Danfoss AK-PC530 / Carel PCO3 )
High pressure side
MT
LT
I.D. FUNCTION
R404A
bar (°C)
R404A
bar (°C)
CONDENSER FAN START
20,4
(+47,0)
20,4
(+47,0)
PSA
2
UTQ39040 -SHEET
4
DIFFERENTIAL 3,0
3,0
1
High pressure switch KP5, manual-reset, adjustable-setting, for backup mechanical operation in the event of controller failure (condenser fan
control).
2
High pressure switch KP5, manual-reset, adjustable-setting, for backup mechanical operation in the event of controller failure (condenser fan
control).
Summary of Contents for EPTAGLOO
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......