where:
V =
is the air flow rate in liters per second;
m =
is the mass in kilos of the refrigerant fluid with the greatest charge, having one part
whatsoever in the dedicated plant room;
14 = is the conversion factor
The ventilation system must renew the air in the room 15 times per hour.
It must be possible to operate the fans from both inside and outside the plant room, and when the
special plant room is installed in a basement, the outside plant room control switch must be on
ground floor.