![background image](http://html1.mh-extra.com/html/costan/eptagloo/eptagloo_installation-user-and-maintenance-manual_2671008011.webp)
COSTAN TECHNICAL DOCUMENTATION
REVISION STATUS
TRUE COPY
PAGE 8 OF 22
PRODUCT:
EPTAGLOO
ORD
DATE
CHANGE ORDER
OF THE SIGNED
DATE OF 1st ISSUE
A
18.Dec.2008
UPDATING
ORIGINAL
13/June/07
DOC. no. QSM0000406A
CHAP. No.:
020
B
28.July.2009
UPDATE OF. SF ENTERING
OF. NC
CHAPTER:
DESCRIPTION / TECHNICAL
C
23.Feb.2010
RANGE
EXTENSION
DETAILS
D
11.Nov..2010
SAFETY VALVE ADDED
ISSUED BY MKT
Medium-temperature applications – 3 Bitzer compressors
TAB.2A
Pack model
3 X 4FC-3.2Y
3 X 4EC-4.2Y
3
X
4DC-5.2Y
Power voltage
400 / 3 / 50
400 / 3 / 50
400 / 3 / 50
Number of compressors
3
3
3
Refrigerant
R404A R404A R404A
Heat extraction rate
1
(W)
28560
35610
43560
Power input
1
(W)
12300 14800 17850
Maximum power
2
(W)
15450 18390 22200
Maximum power input
3
(A) 27,6 32,1 40,5
Pipework
Cond. discharge diameter (mm)
28
35
35
Diameter of condenser return line (mm)
28
35
35
Diameter of suction line (mm)
42
54
54
Dimensions and weights
4
Length
(mm)
2070 2070 2070
Width (mm)
990
990
990
Height
(mm)
1380 1380 1380
Weight (kg)
735
742
756
Compressor
4FC-3.2Y 4EC-4.2Y 4DC-5.2Y
Type
semi-hermetic reciprocating
semi-hermetic reciprocating
semi-hermetic reciprocating
Brand
Bitzer Bitzer Bitzer
Series
Octagon Octagon Octagon
Bitzer lube
BSE 32
BSE 32
BSE 32
Power input under operation
1
(A)
7,48
8,34
10,47
Max. power input
3
(A)
9,2
10,7
13,5
Liquid receiver vessel
Volume of liquid receiver vessel (L)
40
40
40
Diameter of liquid line (in/out) (mm)
22
22
22
Electrical panel (400/3/50)
Code of el.panel with OCD (overcurrent
protection)
UQ391AM8E UQ391AM9E UQ391AM8E
Code of el.panel with RCBO
UQ391AD8E UQ391AD9E UQ391AD8E
Range of overcurrent device to protect
compressors
(7 - 10)A
(9 – 12,5)A
(11 - 16)A
Carel Controller
IR32Z3 IR32Z3 IR32Z3
Danfoss Controller
EKC331/T EKC331/T EKC331/T
Carel Controller
PCO3 PCO3 PCO3
Danfoss Controller
AK-PC530 AK-PC530 AK-PC530
Carel Controller
mRACK
mRACK
mRACK
1
Data calculated using software Bitzer 5.0 at conditions Te=-10ºC ; Tc=+40ºC ; Suction gas temp. =20ºC ; liquid subcooling 0K (pursuant to
Directive EN12900).
The value for the power input does not include condenser fans, which are optionally fitted on the enclosure; it only refers to compressors and does
not consider power-factor improving capacitors.
2
Data calculated using software Bitzer 5.0 at limit use conditions for the specified compressor
3
Technical data for Bitzer compressors as in document KP-100-5i
4
The data in the table refer to the version with enclosure and complete oil circuit
Summary of Contents for EPTAGLOO
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......