040 - INSTALLATION
Take the protective cardboard packaging (if provided) off the equipment and position this
wherever it is to be installed. Then remove both handling skids. Being potentially hazardous,
packaging components (plastic bags, polystyrene, cardboard, nails, etc.) must never be left within
the reach of children, but must be disposed of in accordance with applicable regulations.
For correct operation it is important to lay the
machine horizontally.
Use shims to correct any unevenness existing
on the laying surface. Take the enclosure
panels (if any) off the equipment and then
check that this is level
with reference to a
spirit level rested on the suction header
support
.
Then secure the system to the base stiffly
using screw anchors and the fastening holes
on the machine’s vibration dampening pads.
Put the enclosure panels back in place.
Installation in machine rooms
Non-standard plant rooms must satisfy the requirements established by standards EN 378-3. The
provisions concerning dimensions, construction, accessibility and ventilation must be especially
complied with.
If the plant room enjoys
natural ventilation
, the total area of natural ventilation openings must
be at least (EN378-3:2002 5.5):
A =
0,14 x m
1/2
where:
A =
is the free opening in square meters;
m =
is the mass in kilos of the refrigerant fluid with the greatest charge, having one part
whatsoever in the dedicated plant room;
0,14= is the ratio between the area and the mass – in square meters – divided by the square root
of the kilos
The free flow of air from windows, grids and outlets or pipework must not be hampered by walls
or barriers, enclosing walls, buildings or other means of obstruction. Mind the density of the
refrigerating fluid.
Mechanical ventilation
, if any, must be ensured by fans able to exchange the air in the plant
room, and at least:
V =
14 x m
2/3
Summary of Contents for EPTAGLOO
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......