ONE SD-LAN Wall  
Mount Splitter Housing 
(1LAN-SPLT-132-486C) 
 

STANDARD RECOMMENDED PROCEDURE 000-000-AEN | ISSUE 1 | MARCH 2018 I 

Page 3 

4.1  Wall Mounting PSU6 (Remote Power Option) 

Step 1

 

Remove the rack-mounting brackets and set the 
screws aside. 

 

Figure 3 Dual Gang Box Mounting 

Step 2

 

Using the four screws (previously set aside), 
assemble the wall-mount brackets onto the sides 
of the PSU6 so that the unit can be mounted 
belly-to-wall. See Figure 3. 

Notes: The unit should be mounted on the wall 

with the DC connectors facing sidewards. See 

Figure 5. Make sure that there is enough space 

at the rear to insert/extract the PSMs. 

Step 3

 

Using the wall-mount bracket keyholes as a 
guide, mark the holes to be drilled on the wall. 
Mount the PSU 7 inches horizontally from the 
Wall Mount Splitter Housing. See Figure 4 

Notes: This distance will affect the strip lengths 

of the composite drop cables. If mounting is more 

than 7 inches from splitter housing strip lengths 

wil Need to be adjusted to allow for necessary 

copper conductor length to reach PSU6 power 

ports 

Step 4 

Insert appropriate bolts and mount unit. 

 

 

Figure 4 Housing and PSU6 Wall Mounting 

 

 

Summary of Contents for 1LAN-SPLT-132-486C

Page 1: ...ONE SD LAN Wall Mount Splitter Housing 1LAN SPLT 132 486C STANDARD RECOMMENDED PROCEDURE 000 000 AEN ISSUE 1 MARCH 2018 I Page 1 CMA 477 AEN 1 General Figure 1...

Page 2: ...lan Choose a vertical surface near approved ground but away from downspouts permanent water sprinklers or other water sources Ensure the housing is easily accessible from the front to allow technician...

Page 3: ...mounted on the wall with the DC connectors facing sidewards See Figure 5 Make sure that there is enough space at the rear to insert extract the PSMs Step 3 Using the wall mount bracket keyholes as a g...

Page 4: ...4 5 Accessing the Housing Step 1 Use a 3 8 in can wrench to loosen the security screw on the front cover Figure 5 ONT Fiber Port Step 2 Depress the access latches on the side of the unit and open the...

Page 5: ...ocal practices and ensure proper sealing Feed the end point cables into the housing through the fitting Figure 6 Step 2 Strip 65 inches of the feeder cable jacket with proper cable entry tools Step 3...

Page 6: ...mmend the use of safety glasses spectacles conforming to ANSI Z87 for eye protection from accidental injury when handling chemicals cables or working with fiber Pieces of glass fiber are very sharp an...

Page 7: ...in counter clockwise direction Step 4 Place spiral wrap around the bundle of fibers where they will transition from the bottom chamber to the customer drop adapter field Secure spiral wrap to inner s...

Page 8: ...AN SPLT 132 486C STANDARD RECOMMENDED PROCEDURE 000 000 AEN ISSUE 1 MARCH 2018 I Page 8 Figure 9 8 Connecting End point Connectors during Initial Installation Step 1 Select the appropriate connector f...

Page 9: ...Section 6 to connect end points 10 Connector Care and Cleaning WARNING Isopropyl alcohol is flammable with a flashpoint at 54 F It can cause irritation to eyes on contact In case of contact flush eye...

Page 10: ...cate fiber events and measure the losses attributable to cable connectors splices and or other components The graphical display of loss over a cable s entire length provides the most revealing analysi...

Reviews: