System Monitor
Click the System Monitor tab on the Cell Connection page to access the configuration of additional self-monitoring
for the modem in order to determine when service provider connections may have been terminated.
Figure 18 Cell Connection–System Monitor
Cell Connection Monitor
Reset on Extended
Loss
Fixed-point connections expect to have consistent access to the cellular network,
as compared to mobile connections that may temporarily lose access depending on
coverage. This option causes the modem to reset if the cell connection is lost for
more than the Signal Loss Timeout specified.
Signal Loss Timeout
When Reset on Signal Loss is enabled, enter a timeout period between 90 and 65535
seconds.
Periodic Reset Timer
Periodic Reset Type
Sets the Periodic Modem Reset timer to an Interval of time, a Scheduled day, or
disables the timer.
Interval Length
Sets the Periodic Modem Reset time from 15 to 65,535 min. The Periodic Reset is
disabled when set to 0. Default is set to 4320 min (approximately 3 days).
Scheduled Time
Sets the Periodic Modem Reset to occur at the specified time. Select specific days
of week or select “All” for daily reset. Time is specified as Local Time, based on the
location of the modem itself. The modem’s current time is shown on the home page.