21
The image below displays how the terminals should look after installation.
Figure 1-6
DC Cable Connections
Grounding:
The grounding lug located on the sidewall of the inverter at the DC terminal end is
used to connect the inverter chassis to the battery system’s negative connection or grounding bus, as
required by electrical regulations. The wiring used for grounding should be bare copper or provided
with green insulation. THIS LUG IS NOT FOR AC GROUNDING. For heavy trucks or recreational
vehicles: use copper wire and connect it between the inverter grounding lug and the vehicle’s DC
grounding point (vehicle chassis or assigned grounding bus). Tighten to 6.6 - 7.3 Nm.
STEP 7: OPTIONAL - Mount removable display in remote location
(25ft max)
The communications cable for optional mounting of the display should be at maximum 25 feet.
Mounting the display flush into a wall or panel requires an opening about 3.25in x 1.25in and
1.5in deep (8.25cm x 3.18cm and 3.81cm deep).
Mounting the display panel:
1.
The location for the panel should be dry, out of direct sunlight, free of corrosive fumes,
and suitable for mounting an electronic device.
2.
Draw the area to cut away with a pencil on the wall.
3.
Cut away the area and pilot-drill the mounting holes into the wall.
4.
Put the communication cables into the wall and route to the opening.
5.
The cable connector can be placed in either jack on the panel.
6.
Put the panel in the opening and fasten it into the wall securely.