29
Utility to Inverter
AC input recovery from
Inverter to Utility
100 VAC
Utility to Inverter and
Inverter to Utility
hysteresis
5 VAC minimum
Maximum AC output by‐
pass current
20 Arms
AC transfer time –
Inverter to Utility
20 Seconds nominal
AC transfer time –Utility
to Inverter
< 50 ms
Time delay on transfer
from Inverter to Utility
20 s +/‐ 2s
Vo/‐ 5V
Battery
Charger
AC input operating range
95 – 135VAC
AC input range with full
power
105V – 135VAC
AC input current with no
load
< 0.50 Arms
Input current full load
< 6 Arms (12‐110‐1000‐B2)
11.5 Arms (12‐110‐1000‐B4, 12‐110‐1800‐B4)
AC input frequency
60 Hz +/‐ 1 Hz
Operating Temperature
Range
0C to +50C (Allow for 1.5 Adc charge current reduction above +40C)
DC Output Voltage:
Battery Type
Setting
O/P Voltage VDC (Tol/- 0.2Vdc)
Bulk
Absorption
Float
Fixed 13.5
13.5
13.5
13.5
Flooded
14.4
14.4
13.5
Gel
14.3
14.2
13.8
AGM
14.4
14.3
13.4