27
Charging Current Guidelines
AC Input Circuit
Branch Breaker
or fuse size
(Amps)
Charger DC Current Setting (Amps)
Maximum By-pass AC Current
Available (Amps)
12-110-1000-B2
12-110-1800-B4,
12-110-1000-B4
12-110-1000-B2
12-110-1800-B4,
12-110-1000-B4
15
2 2 13.5
13.5
5 10 12.5
11
10 20 11 8.5
20 40 8.5 3.5
20
2 2 18.5
18.5
5 10 17.5
16
10 20 16 13.5
20 40 13.5 8.5
30
2 2 28.5
28.5
5 10 27.5
26
10 20 26 23.5
20 40 23.5
18.5
Table 3-1
Charging Current Guidelines