Cool Energy EcoStore - Heat Pump Water Heater
EN
17 |
P a g e
3.1.1 Hydraulic safety unit
(mandatory)
You must install all
safety components supplied in the G3 kit
to comply with Building
regulation G3 or with equivalent standards in force including:
- Multiblock Pressure reducing / check / safety valve
- Temperature & Pressure relief valve to cylinder
- Expansion vessel
- Tundish
The above components are required to safely run the supplied equipment. The rated calibration
pressure of the temperature and pressure relief valve must be of 0.6 MPa (6 bar). Pay attention
while installing the safety components, avoiding forcing or alteration. You need to install a
discharge pipe, with a constant downward slope, in a condensate- and ice-free area. There must
be no obstructions in the pipe, to avoid overpressures.