Counter Clockwise Rotation Shown, Rectangular Base
with Curb Cap, Inlet Plenum, Discharge Stack and Stand

27 1/8" Outside

48 1/2" Outside

Discharge

Stack

Inlet

Plenum

Existing

Curb

 

Data 

 

120 CP-BK

 

3

2

 

120 CP-BK

 

CFM

OV

FPM

0.250 SP

0.500 SP

0.750 SP

1.000 SP

1.250 SP

1.500 SP

1.750 SP

2.000 SP

2.250 SP

2.500 SP

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

500 961

802   .03 1018   .07 1220   .11 1396   .15

600 1154 879   .04 1060   .08 1243   .12 1413   .17 1567   .22 1708   .27
700 1346 953   .06 1128   .09 1280   .14 1437   .19 1586   .24 1724   .30 1852   .35 1973   .42
800 1538 1017   .07 1205   .11 1340   .16 1474   .21 1612   .27 1745   .33 1871   .39 1989   .45 2101   .52 2208   .59
900 1730 1076   .09 1282   .14 1414   .19 1532   .24 1651   .30 1773   .36 1894   .42 2010   .49 2120   .56 2225   .63

1000 1923 1150   .11 1355   .16 1492   .22 1603   .27 1708   .33 1815   .40 1925   .46 2035   .54 2143   .61 2245   .68
1100 2115 1234   .13 1420   .19 1568   .25 1680   .31 1779   .37 1874   .44 1971   .51 2071   .58 2171   .66 2271   .74
1200 2308 1321   .16 1476   .22 1642   .28 1758   .35 1855   .42 1945   .49 2033   .56 2121   .64 2211   .71 2303   .80
1300 2500 1410   .19 1539   .25 1710   .33 1833   .40 1933   .47 2021   .54 2104   .62 2184   .69 2265   .78 2347   .86
1400 2692 1501   .23 1615   .29 1769   .37 1906   .45 2009   .52 2099   .60 2180   .68 2257   .76 2332   .84 2406   .93
1500 2885 1592   .27 1697   .34 1826   .42 1973   .50 2084   .58 2175   .66 2258   .75 2333   .83 2405   .92 2475   1.01
1600 3077 1683   .32 1783   .39 1891   .47 2033   .56 2155   .65 2251   .73 2335   .82 2411   .91 2482   1.00
1700 3269 1776   .37 1871   .45 1966   .53 2089   .62 2221   .71 2324   .81 2410   .90 2488   1.00
1800 3462 1868   .43 1960   .51 2048   .60 2151   .69 2280   .79 2393   .89 2484   .99
1900 3654 1961   .50 2050   .58 2132   .67 2222   .76 2336   .86 2456   .97
2000 3846 2055   .57 2141   .66 2219   .75 2299   .84 2397   .95 2513   1.06
2100 4038 2148   .65 2232   .75 2307   .84 2382   .94 2467   1.04
2200 4231 2241   .74 2323   .84 2397   .94 2468   1.04
2300 4423 2337   .83 2415   .94 2486   1.04
2400 4615 2431   .94 2508   1.05

 

Performance shown is for Installation Type B: Free Inlet, Ducted Outlet. Power rating (BHP) does not include drive losses. Performance ratings do not include the 
effects of appurtenances in the airstream.  *Outlet velocity (OV) in feet per minute (FPM) at discharge stack.

 

Wheel Diameter

 

 - 12”

 

Wheel Type

 

 - Flatblade

 

Tip Speed (FPM)

 

 = 3.21 x RPM

 

Max. BHP

 

 = .068 x (RPM/1000)

 

3

 

Plenum Inlet Area

 

 = 1.95 Sq. Ft.

 

Outlet Area

 

 = .52 Sq. Ft.

 

Outlet Velocity* (FPM)

 

  = CFM/.52

 

Max. Motor Frame 

 

- 184T, Arr. 10

 

Approx. Ship Wt. 

 

- 270 lbs. with 

motor and drives as complete unit. 

 

CP-BK 

 

Information

 

 

 

Flow (CFM)

Static Pressure

(In W.G.)

0

600

1200

1800

2400 3000

2.5

2.0

1.5

1.0

0.5

0

 2527 RPM

 .334 HP

 802 RPM

 .5 HP

 2350 RPM

 .75 HP

 2150 RPM

 1 HP

 1950 RPM

 1.5 HP

 1750 RPM

 1550 RPM

 1400 RPM

 1200 RPM

 

A custom Cook CP continuously welded steel, arrangement
10 utility set.

Exhaust fan package is factory assembled, balanced and
test run.

Curb mounted inlet plenum designed for maximum ef

fi

-

ciency and minimal static pressure loss.

Discharge stack to assure high velocity exhaust plume.

Tested for continuous operation at 500

˚

 F.

Listed for both UL 705 (Safety Standard for Power Ventila-
tors) and UL 762 (Power Roof Ventilators for Restaurant
Exhaust Appliances).

Features an “Easy Clean” 

fi

nish utilizing a durable, high

temperature, non-stick cookware coating.

Easy access for cleaning to inlet plenum and ductwork with
quick release latches and large removable panel.

Easy access to fan wheel with hinged discharge stack quick
release latch.

Aluminum grease trough is positioned directly under fan
drain and is easily removable for cleaning.  Grease trough
includes rainwater over

fl

ow feature.

Adjustable aluminum legs to support fan at NFPA 96
required discharge height.

Curb cap and support legs designed to 

fi

t existing BK curb.

All bolted connections sealed with a durable silicone adhe-
sive material rated for 600

˚

 F continuous operation.

Quick release inspection panels on power assembly hous-
ing allow inspection of motor and belts without removing
weather cover.

Lifting lugs are provided for safe installation.

Roof penetration is sealed from the elements.

Summary of Contents for CP-BK

Page 1: ...4 CP BK 2015 E DALE STREET SPRINGFIELD MO 65803 4637 417 869 6474 FAX 417 862 3820 lorencook com BK Broiler Exhaust Fan February 2002...

Page 2: ...let Power rating BHP does not include drive losses Performance ratings do not include the effects of appurtenances in the airstream Outlet velocity OV in feet per minute FPM at discharge stack Wheel D...

Page 3: ...tates in same direction as the arrows on the motor or belt drive assembly Poor fan inlet conditions There should be a straight clear duct at the inlet Improper wheel alignment Excessive Vibration and...

Page 4: ...2527 1 foot 1 4 inch Figure 3 Wheel Rotation Test the fan to ensure the rotation of the wheel is the same as indicated by the arrow marked Rotation 115 and 230 Single Phase Motors Fan wheel rotation...

Page 5: ...or Outdoor Use conduit box Wire shall be ran through UL Listed for Outdoor Use conduit and connectors Notes for Current Sensor 1 Typical operation Line voltage applied continuously After seven seconds...

Page 6: ...change T 5 and J 10 leads To reverse High Speed interchange leads T11 and T12 Low Speed interchange leads T1 and T2 Both Speeds interchange any 2 line leads T 1 T 4 Ground B L2 L1 Ground A Line Ground...

Page 7: ...change T 5 and J 10 leads To reverse High Speed interchange leads T11 and T12 Low Speed interchange leads T1 and T2 Both Speeds interchange any 2 line leads T 1 T 4 Ground B L2 L1 Ground A Line Ground...

Page 8: ...or Outdoor Use conduit box Wire shall be ran through UL Listed for Outdoor Use conduit and connectors Notes for Current Sensor 1 Typical operation Line voltage applied continuously After seven seconds...

Page 9: ...2527 1 foot 1 4 inch Figure 3 Wheel Rotation Test the fan to ensure the rotation of the wheel is the same as indicated by the arrow marked Rotation 115 and 230 Single Phase Motors Fan wheel rotation...

Page 10: ...tates in same direction as the arrows on the motor or belt drive assembly Poor fan inlet conditions There should be a straight clear duct at the inlet Improper wheel alignment Excessive Vibration and...