1
st
Issue 09/05 4
DMP026E
Ex. 2 Programme: Monday to Friday on 08, off 12, on 13,30 on 17, Saturday on 08, off 13,
Sunday off
On
Off
On
Off
Monday, Tuesday,
Wednesday,
Thursday, Friday
08:00
12:00
13:30
17:00
Saturday
08:00
13:00
13.00
13.00
Sunday
00:00
00:00
00:00
00:00
In order to edit the set values of the required variables or, simply to monitor values of the
variables and sets, refer to the Menu description below.
Consider that the analogue inputs, which are not connected, are displayed as ------, the
digital ones are marked by Off.
Installation
Product Description
The DG500 Controller has a moulded polycarbonate base, protection class IP 40, and a LCD
screen for displaying and entering parameters. Its compact size allows easy inclusion in an
electrical enclosure.
Two Versions of the DG500 Controller are available:
•
the wall mountable version (with or without DIN rail)
•
the panel mountable version, using kit DG510
Inspection
Inspect carton for damage. If damaged, notify carrier immediately. Inspect controller for
damage. Return damaged products.
Requirements
(items not provided)
•
Tools:
•
Drill and bits for panel mounting screws.
•
Digital Volt-Ohm-Meter (DVM.
•
EN 60742 power transformer supplying a nominal 24Vac (20.4 to 30Vac) with a minimum
rating of 10VA, 50/60Hz. In case of more than one controller use a transformer supplying
10 VA x number of controllers.
•
Three No. 10 self-starting screws for wall mounting or 35mm DIN rail for mounting.
Summary of Contents for DG501C
Page 32: ...1st Issue 09 05 32 DMP026E...