1
st
Issue 09/05 24
DMP026E
Sat.+ Amb. 1-5
Select this menu for application from 1 to 5 – primary air management with eventual post-
heating.
Supply T 7
It displays supply temperature.
Fixed SP 8
Value of the fixed (editable) SP for saturation temperature; it is on only if the outside sensor
is not connected. Default value 14°C.
Saturat. Comp. 9
Compensation curve for saturation temperature.
outside t.
saturation SP
20
13
24
15
It is possible to edit and/or add values to the curve. In case it is necessary to delete already
existing value pairs, just set a saturation t. value equal to the preceding one in the table.
Example:
outside t.
Saturation SP
20
13
24
15
28
18
outside t.
Saturation SP
20
13
24
15
28
15
Sat. SP 10
Actual operating Set point for HC and CC coils (read-only).
Amb. T 11
It displays the room temperature. It is present only in applications with post-heating (4 and 5).
Read-only.
Fixed SP 12
Value of the fixed (editable) SP for room temperature; it is on only if the outside sensor is not
connected. Default value 22°C.
Ambient Comp. 13
Compensation curve for room temperature.
15
13
20
24