1
st
Issue 09/05 28
DMP026E
Limit ? 35
This option can be used only with application number 6. If it is set to On, it enables the
minimum loop management on supply. Default value: off
Min. SP 36
This option can be used only with application number 6. Minimum limit (read/write). Default
value 15°C.
Hum. Swh. 37
On/Off humidifier status reading.
Fan 38
Fan output v.
Damper 39
Damper output status reading.
Filter 40
It is On if the pressure variation persists for at least 10 minutes.
Fan Coil
Select this menu for fan coil control.
Heat T. 41
It displays the hot fluid temperature. Read-only.
Fixed SP 42
Value of the fixed (editable) SP for hot fluid temperature; it is on only if the outside sensor is
not connected. Default value 65°C.
Heat Comp. 43
Compensation curve for hot fluid temperature.
outside t.
Hot SP
-5
65
20
23
It is possible to edit and/or add values to the curve. In case it is necessary to delete already
existing value pairs, just set a room t. value equal to the preceding one in the table
Example:
outside t.
Hot SP
-5
65
20
23
40
36
outside t.
Hot SP
-5
65
20
23
40
23
65
23
-5
20