DMP026E

 

 

Limit ? 35 
This option can be used only with application number 6. If it is set to On, it enables the 
minimum loop management on supply. Default value: off 
 
Min. SP 36 
This option can be used only with application number 6. Minimum limit (read/write). Default 
value 15°C. 
 
Hum. Swh. 37 
On/Off humidifier status reading.  
 
Fan 38 
Fan output v. 
 
Damper 39 
Damper output status reading. 
 
Filter 40 
It is On if the pressure variation persists for at least 10 minutes. 
 
 

Fan Coil  

Select this menu for fan coil control. 
 
Heat T. 41 
It displays the hot fluid temperature. Read-only. 
 
Fixed SP 42 
Value of the fixed (editable) SP for hot fluid temperature; it is on only if the outside sensor is 
not connected. Default value 65°C.  
 
Heat Comp. 43 
Compensation curve for hot fluid temperature. 
 
outside t. 

Hot SP  

-5  

 

65 

20 

 

23 

  
 
 
It is possible to edit and/or add values to the curve. In case it is necessary to delete already 
existing value pairs, just set a room t. value equal to the preceding one in the table  
Example: 
 
outside t. 

Hot SP 

-5  

 

65 

20 

 

23 

40 

36 

 
 
outside t. 

Hot SP 

-5  

 

65 

20 

 

23 

40 

 

23 

 
 

65 

23 

-5 

20 

Summary of Contents for DG501C

Page 1: ...61 Fax 39 0107306870 871 E mail info controlli org Web www controlli org User Guide DG501C EUROPEAN COMMUNITY DIRECTIVES This equipment meets all requirements of European Community Directives for Low...

Page 2: ...thods 6 LCD PANEL MOUNTING USING DG510 KIT 7 COMMUNICATION ONLY FOR NETWORKS WITH MORE THAN ONE CONTROLLER 7 ADDRESSING 8 WIRING 8 DG500 Terminal Connections 9 I O Wiring 9 Power Supply Wiring 12 Powe...

Page 3: ...o 9 has been chosen and the relevant connections have been carried out stick the label supplied in the package which identifies the scheme number This has the purpose to make it evident for future int...

Page 4: ...protection class IP 40 and a LCD screen for displaying and entering parameters Its compact size allows easy inclusion in an electrical enclosure Two Versions of the DG500 Controller are available the...

Page 5: ...tions Use screened cables If the cable is installed in areas of high RFI EMI the cable must be in conduit Do not mix network wiring with other types of wiring power DO AO DI or UI Digital Output Preca...

Page 6: ...without DIN rail a Loosen two screws securing terminal cover and remove cover b Lift wall mounting bracket clip located on top back of controller c Using a No 10 self starting screw install top screw...

Page 7: ...7 DMP026E LCD Panel Mounting using DG510 Kit Communication only for networks with more than one controller DG500 can operate as a stand alone device or on larger installations connected to a NCP commu...

Page 8: ...binary address c Power up the controller Example to configure address 37 set switches 1 3 and 6 to ON and the other switches to OFF position Wiring The following electrical connections can be made to...

Page 9: ...SHOCK HAZARD DISCONNECT POWER FROM BOTH THE CONTROLLER AND DIGITAL OUTPUTS BEFORE MAKING TERMINATIONS OR CHANGING CONFIGURATION INPUT JUMPERS Voltage input Note An externally powered 0 to 10Vdc senso...

Page 10: ...monitored Maximum count frequency is once every two seconds 1 Review Precautions section 2 Connect one wire from field contact to desired input terminal Polarity is not important 3 Connect other wire...

Page 11: ...9 05 11 DMP026E 2 Connect one wire from load to be switched to desired input terminal 43 45 47 49 51 or 53 3 Connect other side of load to output terminal 44 46 48 50 52 or 54 230Vac Load Switch by Re...

Page 12: ...Power Supply Wiring Note This product contains a non isolated half wave rectifier power supply and must not be powered by transformers used to power other devices containing non isolated full wave rec...

Page 13: ...er and other devices is effected according to job wiring diagram and national and local electrical codes 2 Verify 24Vac power is provided from a power transformer conforming to EN 60742 and wiring is...

Page 14: ...I4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6 52 51 53 DO5 54 HUMIDITY SW ITCH ROOM DUCT U2 ANTIFR...

Page 15: ...8 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6 52 51 53 DO5 54 HUMIDITY SWITCH ROOM DUCT U2 ANTIFROST THERMOSTAT DIFFERENTIAL PRESSURE SWITCH OUTPUT VALVE C...

Page 16: ...4 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6 52 51 53 DO5 54 HUMIDITY SWITCH ROOM DUCT U2 ANTIFROST THERMOSTAT DIF...

Page 17: ...0V DI1 8 0V DI2 9 0V AI1 0V 10 AI2 AI3 11 0V 0V 12 AI4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6...

Page 18: ...4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6 52 51 53 DO5 54 HUMIDITY SWITCH ROOM DUCT U2 ANTIFROS...

Page 19: ...0V DI1 8 0V DI2 9 0V AI1 0V 10 AI2 AI3 11 0V 0V 12 AI4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6...

Page 20: ...DI2 9 0V AI1 0V 10 AI2 AI3 11 0V 0V 12 AI4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 44 43 45 DO1 47 46 48 DO3 50 49 DO4 DO6 52 51 53 DO5...

Page 21: ...INPUT OUTPUT L1 L2 V Y M STC71L 1 2 7 0V DI1 8 0V DI2 9 0V AI1 0V 10 AI2 AI3 11 0V 0V 12 AI4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19 20 AO1 21 0V 0V AO3 22 0V AO4 DO2 4...

Page 22: ...HVAC SYSTEM 9 ALI OUTPUT OUTPUT L1 L2 V Y M OUTSIDE TEMP T1 STC71L 1 2 7 0V DI1 8 0V DI2 9 0V AI1 0V 10 AI2 AI3 11 0V 0V 12 AI4 13 0V AI5 0V 14 AI6 0V 15 AI7 0V 16 AI8 0V 17 AI9 0V 18 AI10 AO2 0V 19...

Page 23: ...the relevant submenu AHU schedule 2 On Off On Off Monday 00 00 23 59 23 59 23 59 Tuesday 00 00 23 59 23 59 23 59 Wednesday 00 00 23 59 23 59 23 59 Thursday 00 00 23 59 23 59 23 59 Friday 00 00 23 59 2...

Page 24: ...nd or add values to the curve In case it is necessary to delete already existing value pairs just set a saturation t value equal to the preceding one in the table Example outside t Saturation SP 20 13...

Page 25: ...rimary air management with eventual pre heating Amb T 15 It displays la room temperature Read only Fixed SP 16 Value of the fixed editable SP for room temperature it is on only if the outside sensor i...

Page 26: ...ed Default value 22 C Advised value 14 C Preheat Comp 21 Compensation curve for pre heating temperature outside t Pre heating SP 20 20 24 23 40 36 It is necessary to edit such curve with suitable valu...

Page 27: ...oling coil B2 Opening 27 It displays the valve opening percentage read only P Band 28 It displays the loop proportional band read write Default value 15 I Time 29 It displays the loop integral time re...

Page 28: ...persists for at least 10 minutes Fan Coil Select this menu for fan coil control Heat T 41 It displays the hot fluid temperature Read only Fixed SP 42 Value of the fixed editable SP for hot fluid temp...

Page 29: ...delete already existing value pairs just set a room t value equal to the preceding one in the table Example outside t Cold SP 20 12 25 9 40 8 outside t Cold SP 20 23 25 9 40 9 Cool SP 48 Actual opera...

Page 30: ...ntrol Set it back to Off at the end of the test phase Pump FC1 57 It displays the digital output status of the 2 pipe fan coil pump or of hot fluid distribution in four pipe fan coil Pump FC2 58 It di...

Page 31: ...riod It has a priority on any other command Remote 68 It displays the status of the manual stop external switch Read only Display 69 It allows overriding stop from LCD Status 70 It displays the actual...

Page 32: ...1st Issue 09 05 32 DMP026E...

Page 33: ...1st Issue 09 05 33 DMP026E...

Reviews: