44
SM-Universal Encoder Plus User Guide
www.controltechniques.com
Issue Number: 6
6.2
Termination resistors
The encoder input termination resistors cannot be disabled when encoders with SinCos
waveforms are selected. The Marker pulse input termination resistors cannot be
disabled except when one of the following encoders is selected
Ab, Fd, Fr, Ab.SErvo, Fd.SErvo, Fr.SErvo.
By default the termination resistors on the encoder inputs are connected with the
exception of the Marker pulse inputs which are disconnected. The termination resistors
can be can be configured as shown below using encoder termination Pr
x.16
.
The termination resistance when connected (A, A\) = 120
Ω
total.
Terminal
Encoder Input
Pr x.16=0
Pr x.16=1
Pr x.16=2
1, 2
A, A\
Disabled
Enabled
Enabled
3, 4
B, B\
Disabled
Enabled
Enabled
5, 6
Z, Z\, Data, Data\
Disabled
Disabled
Enabled
7, 8, 9, 10, 11, 12
U, U\ V, V\ W, W\
Enabled
Enabled
Enabled