SM-Universal Encoder Plus User Guide
25
Issue Number: 6
www.controltechniques.com
Figure 5-2 Fitting the SM-Universal Encoder Plus
7.
Re-fit the terminal cover to the drive
.
(For removal / re-fitting instructions, see
Unidrive SP Solutions Module Installation Sheet
provided with the Solutions
Module
.
)
8.
Connect the AC supply to the drive.
9.
Set Pr
0.49
to L2
to unlock read only security.
10. Check that Menu 15 (slot 1), 16 (slot 2), or 17 (slot 3) parameters are now available.
11. Check that Pr
15.01
, Pr
16.01
or Pr
17.01
show the correct code for the SM-
Universal Encoder Plus (code = 102).
12. If the checks in steps 10 and 11 fail, either the SM-Universal Encoder Plus is not
fully inserted, or the Solutions Module is fault.
13. If a trip code is now present refer to Chapter 10
Encoder connections
In order to ensure correct operation there are a number of checks which should be
carried out:
•
Ensure the encoder is securely mounted to the motor as spurious operation can
result due to the encoder slipping whilst the motor is rotating.
•
Ensure encoder connections to both the encoder and the Solutions Module
terminals are secured, intermittent connections can result in spurious operation or
the Solutions Module not detecting the feedback signals.
•
Ensure screen and grounding recommendations as specified in Chapter
5.5
on page 28, Encoder, Shield connections of this
User guide are followed to prevent noise being induced on the encoder feedback
signals. Noise induced on encoder feedback cables cannot only result in spurious
operation but in extreme cases can result in encoder failure and/or damage to the
Solutions Modules encoder input.
Check the SM-Universal Encoder Plus is the correct issue and has the correct software.
•
Issue 3 -
V.03.xx.xx
•
Issue 4 -
V.04.xx.xx
NOTE