Commander SE User Guide
Issue Number 5
45
In the 4-20mA or 20-4mA ranges with current loop loss (cL) trip, the Drive will trip on
cL if the input reference is less than 3mA.
If 4-20mA or 20-4mA modes are selected and the Drive trips on current loop
loss (cL), analog reference 1 cannot be selected if the current reference is less
than 3mA.
OFF - direction of rotation controlled by the Run Forward and Run Reverse terminals
On - Direction of rotation controlled by the preset speeds value
(use the Run Forward terminal).
When negative preset speeds are enabled, a negative value entered in parameters 11,
12, 13 and 14 causes the motor to rotate in the reverse direction. If not enabled, all
negative values are treated as zero.
Defines the last fault trip of the Drive.
Defines the second to last trip of the Drive.
Defines the third to last trip of the Drive.
Defines the fourth to last trip of the Drive
Ld - Output current as a % of rated motor load
A - Drive output current per phase in amps
Fr - Drive output frequency in Hz
SP - Motor speed in rpm
Cd - Machine speed in customer defined units
Cd (parameter 23) = Speed (rpm) x parameter 24
NOTE
No.
Function
Type
Limitations
Range
Units
Defaults
17
Enable
negative
preset
speeds
RW
Bit
On, OFF
OFF
EUR
OFF
USA
No.
Function
Type
Limitations
Range
Units
Defaults
18
Last
trip
RO
T, S
-
EUR
-
USA
No.
Function
Type
Limitations
Range
Units
Defaults
19
Trip before
P18
RO
T, S
-
EUR
-
USA
No.
Function
Type
Limitations
Range
Units
Defaults
20
Trip before
P19
RO
T, S
-
EUR
-
USA
No.
Function
Type
Limitations
Range
Units
Defaults
21
Trip before
P20
RO
T, S
-
EUR
-
USA
No.
Function
Type
Limitations
Range
Units
Defaults
22
Load
display
units
RW
T
Ld, A
Ld
EUR
Ld
USA
No.
Function
Type
Limitations
Range
Units
Defaults
23
Speed
display
units
RW
T
Fr, SP, Cd
Fr
EUR
Fr
USA