EMM-µD3h  EMM-µD3h-p  EMM-µD3h-485  instruction manual 

IM380-U v3.1 

pag. 12 / 12

 

TECHNICAL CHARACTERISTICS 

MEASURES AND ACCURACY 
Voltage 

True rms value of the phases voltages and phase to phase in a three phase system 
Total range of measure: 20÷500V trms phase to phase- 380V rms phase-neutral 

– 40÷100Hz 

Visualization (20,0÷500V) - measure accuracy: ±0,5% ±1 digit 

– maximum values management 

Current 

True rms value of phase currents and three phase system value 
Range  of measure: 0,02÷5A trms digit 

– 40÷100Hz 

Visualization 0,02÷999A  - accuracy: ±0,5% ±1-  average and maximum values management 

Frequency 

Frequency of phase L1 

– measuring range: 30÷500Hz 

Accuracy: ±0,5% ±1 digit  

Powers 

Active, reactive and apparent powers of phase and three phase system 
Range of measure: 0,01÷999kW - 0,01÷999kVAr - 0,01÷999kVA 
Accuracy: ±1% ±1 digit - Maximum, average and instantaneous values management 

Power factor 

Phase and three phase power factor 
Range of measure: -0,1÷0,1 / accuracy: ±1% ±1 digit - Maximum and average values management 

Hour meter 

Time metering in hours and decimal of hours 
Range of measure 0,0 ÷ 99999.9 h  / accuracy ±0,5%  

Energy measures 

Active, reactive and apparent energies of the three phase system 
Range of measure:  0÷99999999,9 kWh / kVArh / kVAh class 1 (EN 62053-21) accuracy: ±1% 

AUXILIARY POWER SUPPLY AND INPUTS 
Auxiliary supply 

Standard 230V ±15%  -  optional 110V or  400V ±15%  -  50-60Hz  - max 3VA 

Voltage inputs 

From 20 to 500V phase-phase; permanent ov20% -  input impedance:  1 M

 

3, 4 and single phase wiring 

Current inputs 

From 0,02 to 5A; permanent overload 50% - 

from external CT’s with secondary 5A (optional 1A), 

Primary programmable from 5 to 2000A  -  self-consumption <0,5VA 

INPUTS / OUTPUTS 
Digital outputs 
(only for EMM-µD3h-p) 

Digital output ON-OFF(opto-isolated), 5÷230V ac/dc, max 150mA - insulation: 3kV for 60 seconds 
Proportional pulse emission to the active and reactive energy: 
DO1:      active energy pulse output 
DO2:      reactive energy pulse output  
Programmable pulse weight 0,01-0,1-1-10 kWh/pulse, pulse duration 100÷500 msec, max frequency 5Hz 
Alarm signalling function: Setting of measured parameter and time to trip delay 1 ÷ 900 sec 

serial output 
(only

 

for EMM-µD3h-485) 

One output RS485, baud rate selectable, MODBUS-RTU protocol, baud rate 4800÷19200 
insulation: 3kV for 60 seconds 

GENERAL 
Display, keys 

3 display with red LED 7,5mm each of 3 digits 7 segments 
2 keys for selecting measures and programming , LED bar 10 points 

Mechanical 

Protection degree: IP52 front  -  IP20 enclosure and terminals  -  weight: 0,3 kg approx. 
Screw wiring terminal for maximum cross section cable of 4 mm

2

 

Self- extinguishing plastic enclosure 

– for DIN rail mounting, 3 modules of 17,5mm 

Environment 

Working

 

temperature:-10÷60°C;

 

humidity<95%

 

-

 

Storing

 

temperature:-25÷70°C

 

-

 

Isolation

 

test:

 

3kV

 

for

 

1min. 

Standards of reference 

EN 61326-1; EN 55022; EN 61000-6-2; EN 61000-6-4; EN 61010-1; EN 62053-21 

 

DIMENSIONS 

 

9

0

modular version 35mm
DIN 50022
3 moduls 17,5 mm

52.5

60

55

44

4

5

L1

L2

L3

L

out

SET

electrical multi meter

EMM-µD3

max

avg

VL1

VL2

VL3

N

aux2 aux1

voltage inputs

V aux

S1

S1

S1

S2

S2

S2 Do2

c

Co

B

Do1

A

IL1

IL2

IL3

current inputs

Summary of Contents for EMM-mD3h

Page 1: ...ard version 110V rated 50 60Hz optional version 400V rated 50 60Hz optional version INTRODUCTION The EMM D3h are only featured for local visualising the electrical parameters The EMM D3h p has two dig...

Page 2: ...he terminals aux1 and aux2 The rated supply voltages can be standard Vn 230V 15 50 60Hz under request Vn 110V 15 50 60Hz under request Vn 400V 15 50 60Hz measuring voltage inputs 4 terminals are avail...

Page 3: ...PHASE LINE WITH 3 OR 4 WIRES EMM LOAD aux1 aux2 auxiliary supply VL1 VL2 VL3 N measur ing voltage inputs EMM aux1 aux2 auxiliary supply VL1 VL2 VL3 N measuring voltage inputs EMM aux1 aux2 auxiliary s...

Page 4: ...r wiring the voltage measures input and auxiliary supply F Terminals for wiring the current measures input and the digital output when present in the instrument G LED for indicating of a three phase v...

Page 5: ...or EMM D3h p kWh kVAr pulse Set pulse weight kWh kVAr pulse kWh kVAr pulse kWh kVAr pulse only for EMM D3h p Increase from to mS in step by 100 mS Decrease only for EMM D3h 485 Increase Set address of...

Page 6: ...e connection It s possible to chose 3 wires or 4 wires With the 4 wires connection the neutral parameter are displayed and enabled to use for the digital outputs settings Programming of the synchronis...

Page 7: ...arm In mode the digital output DO1 will emit pulses proportional to the active energy counted while the digital output DO2 will emit pulses proportional to the reactive energy counted The proportional...

Page 8: ...B key pressed to decrease the values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is linked with CT and VT ratios for this re...

Page 9: ...the energy meters are shown with the lighting of the LED kW h indicating the active energy values kWh whilst the lighting of the LED kVAr h are indicating the reactive energy values kVArh The lightin...

Page 10: ...lti meter Visualization page 7 Three Phase Hour counter 520 2 h L1 L2 L3 L EMM D3 electrical multi meter VL N A kW kVAr kVA VL L h Hz out max avg SET P F Visualization page 1 VL1 N L1 on IL1 on L2 kWL...

Page 11: ...max V L3 N max phase current I L1 max I L2 max I L3 max average phase current maximum demand I L1 max avg I L2 max avg I L3 max avg three phase system powers W max VAr max VA max average three phase s...

Page 12: ...dance 1 M 3 4 and single phase wiring Current inputs From 0 02 to 5A permanent overload 50 from external CT s with secondary 5A optional 1A Primary programmable from 5 to 2000A self consumption 0 5VA...

Reviews: