EMM-µD3h  EMM-µD3h-p  EMM-µD3h-485  instruction manual 

IM380-U v3.1 

pag. 11 / 12

 

VISUALISATION PEAK VALUES (MAXIMUM) INSTANTANEUS AND AVERAGE. 

By pressing the 

A

 and 

B

 keys simultaneously the instrument reaches the visualisation of the peak value (maximum): the 

visualised measures selectable by 

B

 key, they will start flashing alternatively with the indication of the type of the maximum 

value. 
The maximum memorised values are of two types: the maximum instantaneous values, memorise the maximum reached 
value of the measured parameter, during at least 1 second, the indicated value will flash alternatively with the message 

 (peak); the average values memorise the average value reached, during the last 

, of the measured 

parameter, the value will flash alternatively with the message 

 (

AVeraGe

)

The integration for the calculation of the values is synchronised at every switch on of the instrument 
The maximum values, which may be selected with the 

B

 key are the following: 

THREE-PHASE SYSTEM 

parameter 

Identification symbol 

Value type 

phase voltage 

L1-N max

 

L2-N max

 

L3-N max

 

phase current 

L1 max

 

L2 max

 

L3 max

 

average phase current (maximum demand) 

L1 max (avg)

 

L2 max (avg)

 

L3 max (avg)

 

three phase system powers 

 W 

max

 

 VAr 

max

 

 VA 

max

 

average three-phase system powers (maximum demand) 

 W 

max (avg)

 

 VAr 

max (avg)

 

 VA 

max (avg)

 

three phase system average powers 

 W 

 (avg)

 

 VAr 

 (avg)

 

 VA 

(avg)

 

 

SINGLE PHASE SYSTEM 

Parameter 

Identification symbol 

Value type 

maximum phase voltage 

L1-N max

 

 

 

maximum phase current 

L1 max

 

 

 

maximum phase powers 

 W 

max

 

 VAr 

max

 

 VA 

max

 

average phase current (maximum demand) 

L1 max (avg)

 

 

 

average phase powers (maxiimum demand) 

 W 

max (avg)

 

 VAr 

max (avg)

 

 VA 

max (avg)

 

average phase powers 

 W 

 (avg)

 

 VAr 

 (avg)

 

 VA 

(avg)

 

 

NOTE relative to measures. 

The refresh time of the displays is below 1 second, with a comfortable reading of the measures, even in presence of sudden variations 
of the measured parameters. 
In case that the indicated measures aren’t reliable or they are absurd, it’s important to check carefully the current and voltage inputs 
connection, so as the phase sequence. Check that current and voltage correspond to the same phase (on input L1 it will be con nected 
phase  voltage  L1  and  the  CT  will  be  placed  on  phase  L1),  thence  terminal  S1 of CT will be wired to the relative terminal S1 on the 
instrument. 

Summary of Contents for EMM-mD3h

Page 1: ...ard version 110V rated 50 60Hz optional version 400V rated 50 60Hz optional version INTRODUCTION The EMM D3h are only featured for local visualising the electrical parameters The EMM D3h p has two dig...

Page 2: ...he terminals aux1 and aux2 The rated supply voltages can be standard Vn 230V 15 50 60Hz under request Vn 110V 15 50 60Hz under request Vn 400V 15 50 60Hz measuring voltage inputs 4 terminals are avail...

Page 3: ...PHASE LINE WITH 3 OR 4 WIRES EMM LOAD aux1 aux2 auxiliary supply VL1 VL2 VL3 N measur ing voltage inputs EMM aux1 aux2 auxiliary supply VL1 VL2 VL3 N measuring voltage inputs EMM aux1 aux2 auxiliary s...

Page 4: ...r wiring the voltage measures input and auxiliary supply F Terminals for wiring the current measures input and the digital output when present in the instrument G LED for indicating of a three phase v...

Page 5: ...or EMM D3h p kWh kVAr pulse Set pulse weight kWh kVAr pulse kWh kVAr pulse kWh kVAr pulse only for EMM D3h p Increase from to mS in step by 100 mS Decrease only for EMM D3h 485 Increase Set address of...

Page 6: ...e connection It s possible to chose 3 wires or 4 wires With the 4 wires connection the neutral parameter are displayed and enabled to use for the digital outputs settings Programming of the synchronis...

Page 7: ...arm In mode the digital output DO1 will emit pulses proportional to the active energy counted while the digital output DO2 will emit pulses proportional to the reactive energy counted The proportional...

Page 8: ...B key pressed to decrease the values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is linked with CT and VT ratios for this re...

Page 9: ...the energy meters are shown with the lighting of the LED kW h indicating the active energy values kWh whilst the lighting of the LED kVAr h are indicating the reactive energy values kVArh The lightin...

Page 10: ...lti meter Visualization page 7 Three Phase Hour counter 520 2 h L1 L2 L3 L EMM D3 electrical multi meter VL N A kW kVAr kVA VL L h Hz out max avg SET P F Visualization page 1 VL1 N L1 on IL1 on L2 kWL...

Page 11: ...max V L3 N max phase current I L1 max I L2 max I L3 max average phase current maximum demand I L1 max avg I L2 max avg I L3 max avg three phase system powers W max VAr max VA max average three phase s...

Page 12: ...dance 1 M 3 4 and single phase wiring Current inputs From 0 02 to 5A permanent overload 50 from external CT s with secondary 5A optional 1A Primary programmable from 5 to 2000A self consumption 0 5VA...

Reviews: