EMM-R4h EMM-
μ
4h
instruction manual
IM441-U v0.7
pag. 9
Programming of the serial parameters (only for vers. with serial output)
On
G
display will appear the message
SET
. The following message will appear on
F
display using the
B
and
C
keys. To
confirm press the
A
key.
8 1
8 data bit / 1 stop bit
PAR
No parity
NO
8 2
8 data bit / 2 stop bit
PAR
No parity
NO
8 1
8 data bit / 1 stop bit
PAR
Even parity
EVE
8 1
8 data bit / 1 stop bit
PAR
Odd parity
ODD
Programming of the Password (
SET PAS
)
The instrument is supplied without password. When a password (from 0002 to 9999) is set, using the
B
(to increase),
C
(to decrease) and
A
(to confirm) keys, only who know this value can to enter in the setup. The password, in fact, is
required all the time that someone try to enter in the setup (pressing the
A
and
B
key at the same time). If the password
is wrong, the message
PASS ERR
will appear on
F
display and the instrument go back to the measures visualization.
To input the password, when required by the instrument, at the enter of the setup, use the
A
,
B
and
C
keys as the same
way done previously.
The menu is cyclic. After the last setting, the instrument go back to the first page of Setup (SETUP). It’s always possible
to come back to measures visualization mode pressing at the same time the
A
and
C
keys.
PEAK VALUES AND ENERGY COUNTERS RESET (
RESET
)
From the measures visualization mode, pressing the
A
and
C
keys simultaneously the message
SETUP
will appear on
F
display, press the key
C
until the message
RESET
appears on the same display. To accede to the menu, press the
A
key. Now it’s possible to select the enabling of cancellation type, by pressing the
C
key, according with following types:
RESET PEA
: all maximum value will be delete.
RESET AVG
: all average and average maximum value (maximum demand) will be delete.
RESET EN
: with
NORMAL
as energy mode (
EN
) the total energy counters will be delete, with
TOT PAR
the partial
energy counters will be delete.
RESET ALL
: to delete all average and maximum values and all energy hours counters.
Entry to menu:
seT UP
seT Up
RESET
SET DO1
SET DO2
SET HR_
--- OFF OFF
(the visualization depends on the settings and the I/O status)
RESET PEA
NO
/
YES
Confirm Reset
Deleting maximum values (max)
RESET AVG
NO
/
YES
Confirm Reset
Deleting average values (avg)
and maximum demand (maxD)
RESET EN
NO
/
YES
Confirm Reset
Deleting energy counters
RESET ALL
NO
/
YES
Confirm Reset
Deleting maximum and average
values, and energy counters
To enable the chosen type, press the
B
key to change the indication on display
G
from
NO
to
yes
.
Confirm enabling cancellation, by pressing the
A
key. The indication on display
G
change from
yes
to
---
.
PROGRAMMING OF THE DIGITAL OUTPUT (
SET DO1
SET DO2
) (only for vers. with digital output)
The DO1 and DO2 digital outputs have three modality of functioning:
PULSE
, alarm (
ALR
) and
REMOTE
command.
The DO1 modality setting is independent from DO2. For example it’s possible to set DO1 on
PULSE
(pulse emission)
and DO2 on alarm mode (
ALR
).
In the menu
SET DO1
and
SET DO2
it’s possible to program the function of all digital outputs. In these menus are
available the following modality:
PULSE
,
ALR
and
REMOTE
.
In
PULSE
mode the digital output DO1 will emit pulses proportional to the active energy counted while the digital output
DO2 will emit pulses proportional to the reactive energy counted. The proportionality will depend from the
PULSE
set in
the
SETUP
and the duration of the impulse is set in the
TPL
voice of the
SETUP
.
The
ALR
modality is divided in two parts:
ALR SYS 3PH
and
ALR SYS 123
. With
ALR SYS 3PH
the digital
output will function as alarm verifying that the three phase value doesn’t exceed the threshold set (
ALR HI
and
ALR
LO
). With
ALR SYS 123
the digital output will function as alarm verifying that the maximum value of the single phases
doesn’t exceed the maximum threshold set (
ALR HI
) and that the minimum value of the single phases doesn’t come
down the minimum threshold set (
ALR LO
). The activation of the alarm output will come after some seconds of delay
set(
ALR DL
).
In the
REMOTE
mode, the output status will be decided from the status of the correspondent MODBUS register (see
protocol modbus manual for EMM).