Programming of the transformation ratio of the external current transformers (

SET CT

The programming of the CT ratio, intended as the ratio between the primary and the secondary circuit (example: with CT 
1000/5 it must be set 200), has to be performed by using the front keys. 
After the enter in the setup (message 

SETUP

 on 

F

 display) pressing the 

C

 key, the message 

seT

 will appear on the 

G

 

display and the message 

CT

 

(Current transformer ratio) on the first 

F

 display; the transformation ratio value (set to 1 by 

the manufacturer) on the second and the third 

F

 display. Press 

B

 or 

C

 keys to increase or decrease the value 

respectively (the variation is performed unit by unit). In order to speed up the operation, keep the 

B

 or 

C

 key pressed, the 

variation will be performed by tens and hundreds. To increase or decrease the value by unit, it is necessary to release 
and to press the button again. To confirm the set value, press the 

A

 button; in this way it is possible to enter the next 

programming. If none key is pressed for 10 seconds, the instrument will automatically leave the programming menu and 
the eventual setting SHALL NOT be stored. 

 

-  Programming of the transformation ratio of the external voltage transformers (

SET VT

After the precedent programming phase, on 

F

 display will appear the inscription 

VT

 (voltage transformer) and the value 

of the transformation rate of the external TV (set to 1 from the constructor), considered as the rate between primary and 
secondary (example with TV 15/0.1 kV the value will be 150). In the same way at the programming of the CT rate will be 
possible to set this value. If the external TV are not used the value to set will be 1. To confirm the value press the 

A

 

button. 

 

If the instrument has not options the programming continues with the set of average time 

AVG T’

 and after with the 

password 

PASS

, then it come back at the first page 

SETUP

. The presence or the absence of the options, neutral 

current, digital output and serial output, will allow the visualization or not of the other settings. 

 

Programming of the average time (

seT AVG T’

After the programming phase previously described, pressing another time the 

A

 key, on the 

F

 display will appear the 

message 

AVG T’

 and the average time settable from 1 to 30 minutes. 

To increase the value press the 

B

 key. To decrease it, press the 

C

 key. To confirm it press the 

A

 key. 

The average time is the time used to calculate the average parameters (

avg

) and the maximum demand (

maxD

). 

 

Programming of the energy visualization type (

seT EN

This setting allows to define the energy visualization type after the visualization of the temperature. 
With 

TOT PAR

 will have the visualization of the partial and total energy counters. With 

NORMAL

 there will be only the 

visualization of total counters (that it’s possible to reset from 

RESET

 menu). 

 

Programming insertion mode (

3PH

In a unbalance three phase system it’s necessary to set 

UN_BAL

 (unbalance) while in a balance system (only one CT 

and only one VT) the correct set is 

BALANC

 (balance). For

 

a

 

single

 

phase

 

insertion

 

it’s

 

necessary

 

to

 

set

 

1PH L3

 

Programming wiring connection mode (

MDE

This setting allows to definite the wiring type connection. It’s possible to chose 3 wires or 4 wires. With the 4 wires 
connection the neutral parameter are displayed and enabled to use for the digital and analog outputs settings. 

 

Programming of the synchronism type (

SYN MDE

In this setting for the synchronization type, it’s possible to choose 

L3

 to use the external frequency (on L3 phase) or 

50

60

 Hz to use the internal clock. 

 

Programming

 

of

 

the

 

weight

 

of

 

the

 

active

 

and

 

reactive

 

energy

 

pulse

 

(

seT

 

PULSE

)

 

(only

 

for

 

vers.

 

with

 

digital

 

output) 

After the above mentioned programming, by pressing the 

A

 key again, the message 

PULSE

 will appear on the 

F

 display 

and the value of the weight of one pulse settable on three phase values: 

0,01

 - 

0,1 

10

 kWh or kVArh (for each 

emitted pulse the instrument will have counted 0,01 - 0,1 - 1 - 10 kWh o kVArh). 
Press the 

B

 key to increase the value or 

C

 key to decrease the value and 

A

 to confirm. 

 

Programming of the duration pulse (

SET TPL

) (only for vers. with digital output) 

The message 

TP

L

 will appear together the value of the duration pulse expressed in mS. It’s possible to select the value 

from 100 mS to 500 mS, with 100 ms steps by using 

B

 key (to increase the value) and 

C

 (to decrease the value). Confirm 

the value pressing the 

A

 key. 

This setting is used by all digital outputs. 

 

Programming of the address for the communication network (

SET ID ADR

) (only for vers. with serial output) 

After the confirm with the 

A

 key of the previous value, the message 

ID aDR

 will appear

 

on 

F

 display; to set the value 

that will identify the instrument when it will be connected in a EIA485 communication network, proceed with the modality, 
already described. The settable values are from 1 to 247. To confirm, press the 

A

 key. 

 

Programming of the baud rate (

SET BDR

) (only for vers. with serial output) 

The following setting is the baud rate. The message 

SET

 appears

 

on 

G

 display, the message 

SET BDR

 on the first two 

parts of 

F

 display to indicate the programming of the baud rate displayed on the third part (L3) of the 

F

 display. To modify 

the value set, it’s necessary to use the 

C

 key to decrease and 

B

 to increase the rate. The values settable are: 

19.2

 => 19200 

baud  - 

9.60

 => 9600 

baud  - 

4.80

 => 4800 

baud 

2.40

 => 2400 

baud 

Press 

A

 to confirm the value displayed. 

Summary of Contents for EMM-M4H

Page 1: ...c OPTIONS internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 V L L...

Page 2: ...tage range of measurable voltage L2 L3 phase to phase power supply 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral 110V 85 145V phase to phase 50 85V phase neutral L3 N phase neutral power supply 230V 300 500V phase to phase 175 290V phase neutral 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the ins...

Page 3: ...TION ON THREE PHASE LINE WITH 4 WIRES AND 3 VT EMM P1 S1 P1 P1 P2 S1 S1 S2 INSERTION ON THREE PHASE LINE WITH 3 OR 4 WIRES on line with 3 wires without neutral or with neutral not supplied the N terminal must not be conneccted LOAD EMM P1 S1 P1 P1 P2 S1 S1 S2 N L1 L2 L3 N L1 L2 L3 ...

Page 4: ... P2 S1 S2 N L1 L2 L3 AMPEROMETRIC INSERTION ON THREE PHASE LINE WITH 2CT AARON insertion VOLTAGE INSERTION ON THREE PHASE LINE WITH 3 WIRES AND 2 VT This voltage insertion is possible only with the version with internal CT t suffix LOAD EMM L1 L2 L3 S2 S2 S1 S1 P2 P2 P1 P1 ...

Page 5: ...INSERTION ON BALANCED THREE PHASE LINE WITH 3 OR 4 WIRES on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 L2 L3 LOAD EMM P1 P2 S1 S2 INSERTION ON SINGLE PHASE Only for models with power supply phase neutral Vaux L3 N N L ...

Page 6: ...D E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the display indicates the type of average or maximum value A C when pressing simultaneously the instrument pass to the following menu instrument programming SETUP energy coun...

Page 7: ...0 kW kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 ...

Page 8: ... energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With NORMAL there will be only the visualization of total counters that it s possible to reset from RESET menu Programming insertion mode 3PH In a unbalance three phase system it s necessary to set UN_BAL unbalance while in a balance system only on...

Page 9: ...um values and all energy hours counters Entry to menu seT UP seT Up RESET SET DO1 SET DO2 SET HR_ OFF OFF the visualization depends on the settings and the I O status RESET PEA NO YES Confirm Reset Deleting maximum values max RESET AVG NO YES Confirm Reset Deleting average values avg and maximum demand maxD RESET EN NO YES Confirm Reset Deleting energy counters RESET ALL NO YES Confirm Reset Delet...

Page 10: ...ress A key to confirm CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT With an alarm modality set it s necessary to select the parameters associated to the alarm output by pressing the B and C keys until the parameter choice appears on the third part L3 of F display and the glowing the corresponding led on the D bar Press A key to confirm the set SET THE HIGH AND THE LOW THRESHOLDS On F display ...

Page 11: ...eresis value With only the LO threshold set the alarm condition is activated when the parameter set in alarm drop below the threshold The digital output is enabled only if the alarm condition remain activated for all delay time set From the activation of the digital output the restore is automatic when the parameter grow above the hysteresis value With both LO and HI threshold set the alarm condit...

Page 12: ...ore time the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digi...

Page 13: ...same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L3 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in corre...

Page 14: ...hase currents I L1 max avg I L2 max avg I L3 max avg max maxD avg maximum of average phase currents max demand three phase power W max avg VAr max avg VA max avg max maxD avg maximum of average three phase powers maximum demand phase currents I L1 avg I L2 avg I L3 avg max maxD avg average phase currents three phase power W avg Var avg VA avg max maxD avg average three phase powers NOTE relative t...

Page 15: ...verter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shielded connection Should it be the case of long distance networks ambiences where there have been placed energy transporting cables or ambiences subject to be electrically disturbed it is suggested to u...

Page 16: ...ires 4 wires and single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weigh...

Reviews: