instruction manual 

IM441-U v0.7 

pag. 13  

MEASURES VISUALIZATION 

The instrument is divided in two distinct section: 
the first is composed by three displays (

F

), by 

A

 and 

B

 keys and by LED bar 

D

; the second (in the low part) is composed by 

G

 display, by 

C

 key and by 

LED bar 

E

The two sections are to consider as two different instruments in a only one 
box, in fact it’s possible to act in a zone without to modify the visualization in 
the other (peak value and energy counters visualization excluded). 
 

Visualization section 1 

The three measures of phases (on L1, L2 and L3), of the parameter 
indicated from the led 

D

 on, appears on 

F

 display. For the measure of the 

phase to phase voltages (V 

L-L

), the three measures are V

L1-L2

, V

L2-L3

, V

L3-L1

It’s necessary to press the 

B

 button to select the parameter that can be displayed and indicated from 

D

 LED. 

Press 

A

 button to see on 

F

 display the three phase value (the average of the single phase of voltage, current, power 

factor and the sum of single phase for the power) of the parameter selected: the led inside the 

A

 key is on. 

To press another time the same key the visualization come back at the phase values. 
The unit of measurement can be expressed in kilo or Mega, in the this case the relative LED is on. 
A sign – on the first digit indicates the visualization of the capacitive power factor (example the reading 

-.95

 indicates a 

power factor of 

0.95

 capacitive) 

Note: If in the Setup the single phase mode (

1PH L3

) is set, all the measures appear on the L3 display. 

 

Visualization section 2 

At the same way of the section 1, press the 

C

 button to select the parameter that can be displayed and indicated from 

E

 

LED. The voltage values are of the three phase system, the frequency is of the L3 channel. 
 

Visualization energy and hours counters 

With the 

C

 key it’s possible to visualize on 

F

 display the active, reactive and apparent energy counters. One segment of 

the right digit of the 

G

 display, in correspondence of the 

kWh

 and 

KVArh

 on the front panel, turn on, to indicate the 

visualization of the active and reactive energy counters. The led 

VA

 and the segment of the right digit of the 

G

 display, in 

correspondence of 

…h

 on the front panel, turn on, to indicate the visualization of the apparent energy counter. To 

complete the visualization the led 

k

 over the 

F

 display could be on. 

This is the visualization if 

NORMAL

 is the set in 

EN

 voice of the setup. Instead if the setting is 

TOT PAR

 on the 

F

 

display will be visualized alternatively the partial and the total active, reactive and apparent energy counters; the first digit 
of the 

G

 display indicates the type of the counter: 

P

 for the partial (the user could be reset it) and 

T

 for the total (it’s no 

possible to reset it). 
 
The right digit of 

G

 display, in correspondence of the 

…h

, turn on, when the visualization of hours counters is active. 

 
The reading of the counters use the 9 digits (maximum reading 99999999.9) of the 

F

 display: the measure is displayed in 

the way that the L1 display will indicate the first 3 digits, the display L2 the seconds 3 digits and the L3 display the last 3. 
For example if: L1=000, L2=028, L3=53.2 the reading is 2853.2 kWh. 

section 1

section 2

k

M

k

V

L-N

L1

L2

L3

L

Hz

electrical

multi meter

V

A

P.F.

W

VAr

VA

V

L-N

L-L

°C

V

L-L

alarm

kWh

kVArh

...h

max

avg

max

maxD

avg

Summary of Contents for EMM-M4H

Page 1: ...c OPTIONS internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 V L L...

Page 2: ...tage range of measurable voltage L2 L3 phase to phase power supply 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral 110V 85 145V phase to phase 50 85V phase neutral L3 N phase neutral power supply 230V 300 500V phase to phase 175 290V phase neutral 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the ins...

Page 3: ...TION ON THREE PHASE LINE WITH 4 WIRES AND 3 VT EMM P1 S1 P1 P1 P2 S1 S1 S2 INSERTION ON THREE PHASE LINE WITH 3 OR 4 WIRES on line with 3 wires without neutral or with neutral not supplied the N terminal must not be conneccted LOAD EMM P1 S1 P1 P1 P2 S1 S1 S2 N L1 L2 L3 N L1 L2 L3 ...

Page 4: ... P2 S1 S2 N L1 L2 L3 AMPEROMETRIC INSERTION ON THREE PHASE LINE WITH 2CT AARON insertion VOLTAGE INSERTION ON THREE PHASE LINE WITH 3 WIRES AND 2 VT This voltage insertion is possible only with the version with internal CT t suffix LOAD EMM L1 L2 L3 S2 S2 S1 S1 P2 P2 P1 P1 ...

Page 5: ...INSERTION ON BALANCED THREE PHASE LINE WITH 3 OR 4 WIRES on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 L2 L3 LOAD EMM P1 P2 S1 S2 INSERTION ON SINGLE PHASE Only for models with power supply phase neutral Vaux L3 N N L ...

Page 6: ...D E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the display indicates the type of average or maximum value A C when pressing simultaneously the instrument pass to the following menu instrument programming SETUP energy coun...

Page 7: ...0 kW kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 ...

Page 8: ... energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With NORMAL there will be only the visualization of total counters that it s possible to reset from RESET menu Programming insertion mode 3PH In a unbalance three phase system it s necessary to set UN_BAL unbalance while in a balance system only on...

Page 9: ...um values and all energy hours counters Entry to menu seT UP seT Up RESET SET DO1 SET DO2 SET HR_ OFF OFF the visualization depends on the settings and the I O status RESET PEA NO YES Confirm Reset Deleting maximum values max RESET AVG NO YES Confirm Reset Deleting average values avg and maximum demand maxD RESET EN NO YES Confirm Reset Deleting energy counters RESET ALL NO YES Confirm Reset Delet...

Page 10: ...ress A key to confirm CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT With an alarm modality set it s necessary to select the parameters associated to the alarm output by pressing the B and C keys until the parameter choice appears on the third part L3 of F display and the glowing the corresponding led on the D bar Press A key to confirm the set SET THE HIGH AND THE LOW THRESHOLDS On F display ...

Page 11: ...eresis value With only the LO threshold set the alarm condition is activated when the parameter set in alarm drop below the threshold The digital output is enabled only if the alarm condition remain activated for all delay time set From the activation of the digital output the restore is automatic when the parameter grow above the hysteresis value With both LO and HI threshold set the alarm condit...

Page 12: ...ore time the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digi...

Page 13: ...same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L3 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in corre...

Page 14: ...hase currents I L1 max avg I L2 max avg I L3 max avg max maxD avg maximum of average phase currents max demand three phase power W max avg VAr max avg VA max avg max maxD avg maximum of average three phase powers maximum demand phase currents I L1 avg I L2 avg I L3 avg max maxD avg average phase currents three phase power W avg Var avg VA avg max maxD avg average three phase powers NOTE relative t...

Page 15: ...verter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shielded connection Should it be the case of long distance networks ambiences where there have been placed energy transporting cables or ambiences subject to be electrically disturbed it is suggested to u...

Page 16: ...ires 4 wires and single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weigh...