Contrel EMM-M4H Instruction Manual Download Page 2

 

EMM-R4h EMM-

μ

4h 

instruction manual 

IM441-U v0.7 

pag. 2  

INSTALLATION 

WARNING FOR THE USER 
Read carefully the instructions/indications contained in this manual before installing and using the instrument. 
The instrument described in this manual is intended for use by properly trained staff only. 
SAFETY 
This instrument has been manufactured and tested in compliance with EN 61010-1standards. In order to maintain these conditions and 
to ensure safe operation, the person must comply with the indications and markings contained in the manual. When the instrument is 
received, before beginning installation, check that it's O.K. And it has not suffered any damage during transport. When starting 
installation make sure that the operating voltage and mains voltage are compatible with the device instructions. The instrument power 
supply must not be earthed. Maintenance and/or repair must be carried out only by qualified and authorized personnel. If there is ever 
the suspicious that, that there is a lack of safety ,during operation, the instrument must be disconnected and cautions taken against 
accidental use. 

Operation is no longer safe when: - The instrument doesn't work. / - The measured value are obviously wrong or 
unreasonable / - There is clearly visible damage. / - After serious damage incurred during transport. / - After a storage under 
unfavourable conditions 

 

CONNECTION 

For a correct use of the device, the wiring diagram contained in the present manual, must be respected. 
The connections are available on the screw terminal: 

 

-  auxiliary power supply: 

The power supply is take from voltage inputs. 
Are available 3 different auxiliary supply: 
 

0 - 115V = 100-130V 50-60Hz 

(N-L3) 

(on request) 

 

0 - 230V = 220-240V 50-60Hz 

(N-L3) 

(on request) 

 

0 - 400V = 380-415V 50-60Hz 

(L2-L3) 

(standard model) 

It’s possible, for example, to give an auxiliary power supply between phase and neutral, in a 4 wires system, or phase-
phase in a 3 wires system, without neutral or from a VT in a medium voltage application. 

In the standard version the voltage is 400V and it’s taken between the phases L2-L3. 

In the following table it’s possible to see the measurable voltage depending of the type of power supply. 

power supply terminals 

rated voltage 

range of measurable voltage 

L2-L3

 (phase to phase power supply) 

400V 

300÷500V phase to phase (175÷290V phase-neutral) 

230V 

175÷290V phase to phase (130÷170V phase-neutral) 

110V 

85÷145V phase to phase (50÷85V phase-neutral) 

L3-N

 (phase – neutral power supply) 

230V 

300÷500V phase to phase (175÷290V phase-neutral) 

110V 

175÷290V phase to phase (100÷170V phase-neutral) 

The standard version allows to apply the instrument at all the three-phase network 400V with or without neutral supplied. 
For example for application on single phase 230V will need the L3-N / 230V. while for applications in medium voltage (for 
example using external voltage transformer 15 / 0.1 kV phase to phase) will need the version L2-L3 / 110V. 

 

-  measure voltage inputs:

 

 

4 terminals are available for the connection to 
the 3 phase and neutral of the network of 
measure, the maximum voltage phase to 
phase shouldn't be over 500 V rms and 
dependent to the auxiliary power supply. In 
case of a 3 phase system without neutral, or 
non distributed neutral to leave terminal N 
free. It’s possible to use external voltage 
transformer in fact the transformation rate of 
the external transducer can be set in the 
SETUP of the instrument and the 
visualization allows the reading of voltage up 
to 40,0 kV. 

 

-  measure current inputs: 

4 terminals are available for the connection to 
3 external amperometric transformers with secondary 5A, it’s possible to use 2 TA on lines with 3 wires (insertion three 
phase Aron). The utilization of external TA is obligatory. The transformation rate of the external transducer can be set in 
the SETUP of the instrument and the visualization allows the reading of voltage up to 9,99 kA. 

 

REMARKS

: It's a must to respect the phase sequence. The connections between current and voltage phase inputs must not be 

inverted (for example, CT placed on phase L1 must correspond to the I1 input). So as it is not correct to invert S1 and S2 terminals, 
since power factors and powers might not be reliable. 
For fixing the flush mount version instrument to the panel, use the fixing devices supplied, by inserting them in the side groves of the 
enclosure and tighten the screws. 
For safety reasons, place an external fuse protection at the input voltages, and use adequate cables for the working voltages and 
currents, with a cross sections from 0,5 to 2,5 mm

2

ENERGY COUNTERS

REAR PANNEL

extractible screw terminal

EMM-R4h

EMM-µ4h

Summary of Contents for EMM-M4H

Page 1: ...c OPTIONS internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 V L L...

Page 2: ...tage range of measurable voltage L2 L3 phase to phase power supply 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral 110V 85 145V phase to phase 50 85V phase neutral L3 N phase neutral power supply 230V 300 500V phase to phase 175 290V phase neutral 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the ins...

Page 3: ...TION ON THREE PHASE LINE WITH 4 WIRES AND 3 VT EMM P1 S1 P1 P1 P2 S1 S1 S2 INSERTION ON THREE PHASE LINE WITH 3 OR 4 WIRES on line with 3 wires without neutral or with neutral not supplied the N terminal must not be conneccted LOAD EMM P1 S1 P1 P1 P2 S1 S1 S2 N L1 L2 L3 N L1 L2 L3 ...

Page 4: ... P2 S1 S2 N L1 L2 L3 AMPEROMETRIC INSERTION ON THREE PHASE LINE WITH 2CT AARON insertion VOLTAGE INSERTION ON THREE PHASE LINE WITH 3 WIRES AND 2 VT This voltage insertion is possible only with the version with internal CT t suffix LOAD EMM L1 L2 L3 S2 S2 S1 S1 P2 P2 P1 P1 ...

Page 5: ...INSERTION ON BALANCED THREE PHASE LINE WITH 3 OR 4 WIRES on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 L2 L3 LOAD EMM P1 P2 S1 S2 INSERTION ON SINGLE PHASE Only for models with power supply phase neutral Vaux L3 N N L ...

Page 6: ...D E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the display indicates the type of average or maximum value A C when pressing simultaneously the instrument pass to the following menu instrument programming SETUP energy coun...

Page 7: ...0 kW kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 ...

Page 8: ... energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With NORMAL there will be only the visualization of total counters that it s possible to reset from RESET menu Programming insertion mode 3PH In a unbalance three phase system it s necessary to set UN_BAL unbalance while in a balance system only on...

Page 9: ...um values and all energy hours counters Entry to menu seT UP seT Up RESET SET DO1 SET DO2 SET HR_ OFF OFF the visualization depends on the settings and the I O status RESET PEA NO YES Confirm Reset Deleting maximum values max RESET AVG NO YES Confirm Reset Deleting average values avg and maximum demand maxD RESET EN NO YES Confirm Reset Deleting energy counters RESET ALL NO YES Confirm Reset Delet...

Page 10: ...ress A key to confirm CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT With an alarm modality set it s necessary to select the parameters associated to the alarm output by pressing the B and C keys until the parameter choice appears on the third part L3 of F display and the glowing the corresponding led on the D bar Press A key to confirm the set SET THE HIGH AND THE LOW THRESHOLDS On F display ...

Page 11: ...eresis value With only the LO threshold set the alarm condition is activated when the parameter set in alarm drop below the threshold The digital output is enabled only if the alarm condition remain activated for all delay time set From the activation of the digital output the restore is automatic when the parameter grow above the hysteresis value With both LO and HI threshold set the alarm condit...

Page 12: ...ore time the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digi...

Page 13: ...same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L3 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in corre...

Page 14: ...hase currents I L1 max avg I L2 max avg I L3 max avg max maxD avg maximum of average phase currents max demand three phase power W max avg VAr max avg VA max avg max maxD avg maximum of average three phase powers maximum demand phase currents I L1 avg I L2 avg I L3 avg max maxD avg average phase currents three phase power W avg Var avg VA avg max maxD avg average three phase powers NOTE relative t...

Page 15: ...verter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shielded connection Should it be the case of long distance networks ambiences where there have been placed energy transporting cables or ambiences subject to be electrically disturbed it is suggested to u...

Page 16: ...ires 4 wires and single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weigh...