Instrument Calibration
515 HC04 - 8 June 2007
51
Warning Messages
The system displays warning messages as described in the following table:
New/Failed Battery -
Set Time
The real-time clock has lost the correct time because the battery has
failed, or there is a new battery. Set the current time and date (in the
TM/LOG menu) to clear the error message and to continue data
logging at the correct times.
Note:
The instrument can continue operating with a failed battery,
but the correct time will be lost if there are interruptions to the
power supply.
Temperature Sensor 1
Failure
The temperature sensor on analog input 1 has failed. To deactivate
the error, the Analog Input Signal Type can be set to DEFAULT to
use a programmed default value instead of the sensor signal.
Temperature Sensor 2
Failure
The temperature sensor on analog input 2 has failed. To deactivate
the error, the Analog Input Signal Type can be set to DEFAULT to
use a programmed default value instead of the sensor signal.
Lo Range Flow Input
Failure
The low range flow transmitter (analog input 3) has failed.
Hi Range Flow Input
Failure
The high range flow transmitter (analog input 4) has failed.
Diameter Ratio is out
of Range
The diameter ratio (beta) is out of the allowed range. The pipe and/or
orifice diameters (specified in the Parameters menu) should be
within the recommended limits of the DP flowmeter being used.
Temperature is Out of
Range
The feed and/or return temperature inputs are outside of the allowed
calculation range.
Error Messages
Description
Warning Messages
Description
Value Has Been Set to
Default
You have entered an invalid value for a parameter. Therefore, the
instrument has set the default value.
Over Total Limit -
Maximum Set
You have exceeded the maximum number of logging entries for the
combined time bases. The instrument has set the current log setting to
the remaining maximum number.
Already Assigned to
Other Port
You have tried to assign a particular protocol type to more than one
serial communication port. The instrument has set the protocol to
NONE.
Summary of Contents for 515
Page 4: ...iv 515 HC04 8 June 2007 ...
Page 8: ...viii 515 HC04 8 June 2007 ...
Page 16: ...Introduction 8 515 HC04 8 June 2007 ...
Page 60: ...Instrument Calibration 52 515 HC04 8 June 2007 ...
Page 80: ...Communications 72 515 HC04 8 June 2007 ...
Page 82: ...74 515 HC04 8 June 2007 ...
Page 88: ...80 515 HC04 8 June 2007 ...