POWER RATINGS
Superterm CIC1800 / CICP1400UL
91
SPECIFICATIONS
Cables
AWG
Type *
Maximum Length
Alarm Inputs
22 ga Stranded, shielded, w/drain 2-
conductor alarm
1000 ft
(305m)
Readers:
Magnetic Stripe &
Wiegand/Proximity
22 ga Stranded, shielded, w/drain 4
or 5-conductor
(5-conductor for readers w/
LEDs)
1000 ft
500 ft w/unbuffered
Wiegand
(305m/152m
unbuffered)
Keypad
22 ga
Stranded, shielded w/drain
7-conductor
1000 ft
(305m)
Polling Line
RS-422 (Network)
22 ga
Stranded, shielded, w/drain
2-twisted pair
4000 ft
(1220m)
RS-232, Dial-Up
(Host Computer)
22 ga
Stranded, shielded, w/drain
50 ft
(15m)
Printer
22 ga Stranded, shielded, w/drain 3-
conductor
50 ft
(15m)
* NOTE:
DO NOT use twisted pair cables except for
RS-422 connections.
POWER RATINGS
As supplied from the factory, the Superterm contains a 115VAC Power Supply, or an optional 230VAC Power
Supply (this option not evaluated by ETL).
Continental Instruments LLC recommends using a dedicated, unswitched power outlet to prevent any
interference from other equipment that might be connected on the same line.
Voltage
Current
(Maximum)
Power
(Maximum)
AC- 105-125VAC
1.0 Amperes
125VA
210-250VAC 0.5
Amperes
DC- 12VDC
0.5 Amperes
Std. Version
6 Watts
DC- 12VDC
1.0 Ampere
Exp. Power Version
12 Watts
Summary of Contents for SUPERTERM CIC1800
Page 27: ...Figure 15 Superterm Circuit Board Relay Location...
Page 53: ...Figure 34 COM1 Terminal Strip Connection...
Page 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Page 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Page 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Page 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Page 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Page 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Page 77: ...Figure 48 Jumper Locations and Settings...
Page 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Page 83: ...Figure 53 256K Memory Upgrade Installation...
Page 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...