AUXILIARY POWER
Superterm CIC1800 / CICP1400UL
36
AUXILIARY POWER
The AUX POWER terminal strip (labeled12_V)
pr12VDC power outlets for a maximum of
three expansion UO option boards or auxiliary
devices. The AUX POWER terminal strip is
located in the lower right-hand corner of the
Superterm circuit board (see Figure 23). For
specific information regarding expansion boards,
refer to page 50, Expansion Input/Output Boards.
Table 24 lists the AUX POWER terminal strip pin
numbers and their associated functions.
Table 24 - AUX POWER (12_V)
Terminal Strip Functions
Pin Function
1 +12
2 GND
3 +12
4 GND
5 +12
6 GND
NOTE:
Combined 5VDC and 12VDC accessory
current draw is limited to a total maximum value of
0.80 Amps for the basic Superterm version
(without Expansion Power Supply). Please see
Capacities
, Page 10.
In the expanded Superterm Version, 12VDC
current draw is limited to a maximum of 1 Amp
(with Expansion Power Supply).
WARNING
Verify that the main power to the Superterm
circuit board is OFF before connecting any
optional devices.
WARNING
Observe Positive and Negative wire polarity
between option boards and the Superterm.
Addi12VDC Power Outlets
The third pin (Pin 3) of the DR1 through DR8
terminal strips pr12VDC to suitable access
control accessories (see Figure 24).
Summary of Contents for SUPERTERM CIC1800
Page 27: ...Figure 15 Superterm Circuit Board Relay Location...
Page 53: ...Figure 34 COM1 Terminal Strip Connection...
Page 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Page 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Page 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Page 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Page 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Page 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Page 77: ...Figure 48 Jumper Locations and Settings...
Page 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Page 83: ...Figure 53 256K Memory Upgrade Installation...
Page 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...