
RELAY CONNECTIONS
Superterm CIC1800 / CICP1400UL
30
LOCAL Power Connection
In LOCAL power mode, a single, external power
supply (28VDC or 28VAC max.) is mounted
outside of and adjacent to the Superterm cabinet.
This supply provides power to a maximum of eight
Superterm door strike relays through the STKPWR
terminal strip located on the lower edge of the
Superterm circuit board (see Figure 17).
Strike power is routed through the Superterm
circuit board to the individual relay connectors,
thus eliminating the need for separate power
supplies at each door.
The STK- input (STKPWR - Pin 4) is routed to
the COMMON (C) relay connection (RLY #X
- Pin 2).
The STK+ input (STKPWR - Pin 3) is routed
through the DIS pins (1 and 2) to the Normally
Open (NO, RLY #X - Pin 1) or the Normally
Closed (NC, RLY #X - Pin 3), depending on
the state of the relay.
A Normally Closed (NC) emergency switch may
be used in conjunction with the Local power mode
to disconnect the strike power upon an emergency
situation.
NOTE:
Operating a door strike relay in the
LOCAL mode requires setting two jumpers per
relay. Refer to page 72 for specific information
about setting the door strike jumpers.
All door strike relays connected in the LOCAL
power configuration operate from the same power
source and must have the same voltage rating.
All strike relay circuits (odd numbered relays) are
individually fuse protected in both the LOCAL or
the REMOTE configuration.
If an emergency sensor is not used, install a jumper
between Pin 1 (DIS) and Pin 2 (DIS) on the
STKPWR terminal strip.
Table 16 lists the connections between the
STKPWR terminal strip and the external power
supply (see Figure 17).
Table 16 - Connection Table for External
Power Supply
Power Supply
STKPWR Terminal Strip
Positive ((B)
Pin # 3
Negative (-)
Pin #4
Emergency Sensor Connection
An external emergency sensor may be used to
disconnect the LOCAL strike power supply if an
emergency condition is detected.
The emergency sensor is placed in series with the
STK+ signal by connecting it between Pin 1 and
Pin 2 of the STKPWR terminal strip (see Figure
18).
NOTES:
The emergency sensor must be a
Normally Closed (NC) switch and the strike relays
must be wired in a Normally Closed (NC)
configuration (refer to page 26, LOCAL Power
Door Strike Connection).
If an emergency sensor is not used, place a jumper
between Pin 1 and Pin 2 on the STKPWR terminal
strip (see Figure 17).
Table 17 - Connection Table for Emergency
Sensor and
External Power Supply
Device
STKPWR Terminal Strip
Emergency Sensor
Pin #1 (DIS)
Emergency Sensor
Pin #2 (DIS)
Power Supply Positive (0)
Pin #3 (STY, +)
Power Supply Negative (-)
Pin #4 (STK -)
NOTE:
Normally Closed (NC) emergency sensor
connections are not sensitive to polarity.
Summary of Contents for SUPERTERM CIC1800
Page 27: ...Figure 15 Superterm Circuit Board Relay Location...
Page 53: ...Figure 34 COM1 Terminal Strip Connection...
Page 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Page 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Page 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Page 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Page 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Page 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Page 77: ...Figure 48 Jumper Locations and Settings...
Page 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Page 83: ...Figure 53 256K Memory Upgrade Installation...
Page 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...