UM-15093500-AA1
Page
34
On-Off Control
BV 5
R/W
On/Off Status of Thermostat
0: Off, 1: On
Temperature Scale
BV 6
R/W
°C/ °F
0: °C
1: °F
Relay 1 Control
BV7
R/W
On/Off Control of Relay 1
0: Off, 1: On
Relay 2 Control
BV8
R/W
On/Off Control of Relay 2
0: Off, 1: On
Relay 3 Control
BV9
R/W
On/Off Control of Relay 3
0: Off, 1: On
Relay 4 Control
BV10
R/W
On/Off Control of Relay 4
0: Off, 1: On
Relay 5 Control
BV11
R/W
On/Off Control of Relay 5
0: Off, 1: On
Relay 6 Control
BV12
R/W
On/Off Control of Relay 6
0: Off, 1: On
Relay 7 Control
BV13
R/W
On/Off Control of Relay 7
(Fan)
0: Off, 1: On
Occupancy
Command
BV 14
R/W
Room Occupancy Setting
0: Occupied,
1: Unoccupied
Fan Output for
Heating
BV15
R/W
Disable/ Enable Fan
Output for Heating
0: Disable
1: Enable
Heartbeat
BV16
R/W
Communication
Heartbeat Flip-Flop
0: Off
1: On
Fan Mode
MSV 0
R/W
Fan Mode
1: Auto 2: Low
3: Med
.
4: Hi
System Mode
MSV 1
R/W
Working Mode: Heat, Cool or
Ventilation
1: Cool Mode
2: Heat Mode
3: Ventilation @ Cool Mode
4: Ventilation @ Heat Mode
Sleep
MSV 2
R/W
Sleep (Only for Models with
Sleep Function Available).
1: Disable,
2: 0 Hr. Sleep
3: 0.5 Hr. Sleep
4: 1 Hr. Sleep
5: 1.5 Hrs. Sleep,
6: 2 Hrs. Sleep
Temperature Source
MSV3
R/W
Current Temperature Source
1: Built-In Temp. Sensor
2: Remote Temp. Sensor
3: Assigned through BACnet
Lowest Fan
Speed
MSV 4
R/W
Lowest Fan speed in
Auto Fan mode
1: Stop 2: Low
3: Med. 4: Hi
Fan Speed Status
MSV 5
R
Fan Speed Status
0: Stop 1: Low
2: Med
3: Hi
Display Options
MSV 6
R/W
LCD Display Options
1: T & Time (if available) 2:
SP & Time (if available) 3: T
& CO2 (if available)
4: CO2 & Time (if available)