Page
12
UM-15093500-AA1
User Mode Thermostat Operation
#
Item
Description
Remarks
1
Normal Display
Display current room or set-point
temperature
Use the (
SP
) parameter in the
Engineering Menu or [
MSV6
]
Display
to choose Current room
or Set- point temperature on
display.
2
Temperature
Setpoint Setting
using Up/Down
Arrows
Set the desired temperature
The [
AV0
] / [
AV3
] Cool / Heat
Occupied and [
AV8
] / [
AV9
]
Unoccupied Cool / Heat
temperature setpoints BACnet
objects can be used to write or
force the setpoint to a desired
value from BACnet supervisor.
3
Mode Select
Select the working mode:
Cooling (
), Heating (
)
, or
Ventilating (
)
.
After pressing the MODE button,
press the UP/ DOWN button to
rotate the selections. Dependent
on Control Type.
4
Fan Auto/
Continuous
Change the Fan mode between
Auto or Continuous On.
When AUTO is displayed, the
fan is handled automatically.
When AUTO is flashing, the fan
is working under a delay timer.
When FAN icon is spinning but
AUTO is not displayed, the fan
will run continuously until
commanded off.
5
Occupancy Setting
Press SET, Used UP and DOWN
arrows to toggle between the
Occupied and Unoccupied setting.
Use MODE or SET buttons to
apply.
The SET button could be
locked for applications
forbidding user occupancy
state control.