UM-15093500-AA1
Page
21
Item
Mnemonic
Description
°C Scale
°F Scale
Step
Default
Range
Default
Range
E57
Phy3
MAC address 5th & 6th bytes
hhhh
hhhh
h: 0~F in hex
E58
IP-1
1st byte of IPv4 address
192
0~255
192
0~255
1
E59
IP-2
2nd byte of IPv4 address
168
0~255
168
0~255
1
E60
IP-3
3rd byte of IPv4 address
0
0~255
0
0~255
1
E61
IP-4
4th byte of IPv4 address
1
0~255
1
0~255
1
E62
tESt
Self-Diagnostic – toggle all LCD features and
all relays. Use only to test
Use
Caution!
Press MODE to
engage test
E63
boot
Reset Wi-Fi parameters to factory defaults
Press MODE to
reset
E64
rSt
Reset all parameters including communication
and control algorithm to the factory defaults
Use
Caution!
Press MODE to
reset
E65
End
Exit Engineer Mode Menu
Press MODE to
exit engineering
menu
** Note: 1. Changing these values needs to unlock modification for communication parameters in
advance. Please refer to the parameter LOC(Lock, AV17) for details.
2. Device instance number = “devH” *1000 + “devL” = 0~4194302. ex. If “devH” is 100 and devL”
is 001then the Device instance number = 100001.
Lock Function Setup and Examples
The 16-bit binary encoded decimal register accessed through
Lock
[AV17] BACnet object and LOC
engineering menu item is used to enable/disable features in the thermostat. The first 10 bits are used
(bit 0 ~ bit 9), bits 10~15 are reserved/unused. Bits are represented by their decimal values and are
added or subtracted to toggle from “0” to “1”. Add a bit’s decimal value to toggle to “1” or subtract a bit’s
decimal value to toggle to “0”. See table below.