UM-15093500-AA1
Page
20
Item
Mnemonic
Description
°C Scale
°F Scale
Step
Default
Range
Default
Range
E30
tyPE
Control Type
2
1~2
2
1~2
1: 4-Pipe
cooling or
heating
Manual
Changeover
2: 4-Pipe
heating and
cooling auto
Changeover
E31
OPL2
Minimum Output for AO2
0(0V)
0~125
0 (0v)
0~125
1 (LSB)
(0.044V)
E32
SPA2
Span Offset for AO2
0(0V)
0~125
0 (0v)
0~125
1 (LSB)
(0.044V)
E33
Hrtr
Communication Heartbeat Minimum Rate
60
10~3600
60
10~3600 10s
E34
rhPB
Humidity Control PB
E35
rhdF
Humidity Control Diff.
E37
CO2F
CO2 Offset Value
E38
AFtH
After Hour Extension Time
(not used)
E39
VALL
Input Low Value of Valve Feedback
(not used)
E40
VALH
Input High Value of Valve Feedback
(not used)
E41
OPts
Options
(not used)
E42
dlAb
DI contact Defination
(not used)
E43
Hrt
Communication Heartbeat Flip-Flop
0
0/1
0
0/1
0: Off
1: On
E44
CSPL
Minimum Cooling Temperature Setpoint
18.0
0.0- 50.0
65.0
32.0-122.0 0.1(°C/°F)
E45
HSPH
Maximum Heating Temperature Setpoint
25.0
0.0-50.0
77.0
32.0-122.0 0.1(°C/°F)
E46
nFAn
Minimum Fan Output
(not used)
E47
hFAn
Maximum Fan Output
(not used)
E48
FAnL
Low Fan Speed Setting
(not used)
E49
FAn2
Med. Fan Speed Setting
(not used)
E50
FAnH
Hi Fan Speed Setting
(not used)
E51
ObAb
Humidity Control PB
(not used)
E52
OFFt
Minimum Off Time
180
0~600
180
0~600
5 (seconds)
E53
On-t
Minimum On Time
0
0~600
0
0~600
5 (seconds)
E54
It-2
Integral Time and Output Cycle Time 2
60
0~500
60
0~500
10 (Seconds)
E55
Phy1
MAC address 1st & 2nd bytes
hhhh
hhhh
h: 0~F in hex
E56
Phy2
MAC address 3rd & 4th bytes
hhhh
hhhh
h: 0~F in hex