UM-15093500-AA1
Page
30
Integral-Cycle
Time
AV 10
R/W
Integral Time and Output
Cycle Time
0~500 (Sec.)
Analog Minimum
Output for AO1
AV 11
R/W
Minimum Output Voltage in
Digital Value When Reach
Low Limit for AO1
0~125 (LSB)
Span Offset for AO1
AV 12
R/W
Span Offset for AO1
-55~0 (LSB)
Low Setpoint Limit
AV 13
R/W
Low Limit for Set-Point
Temperature
°C :0~500 (0.0
~
50.0
℃
)
°F: 320~1220(32.0~122.0°F)
High Setpoint Limit
AV 14
R/W
High Limit for Set-Point
Temperature
°C :0~500 (0.0
~
50.0
℃
)
°F: 320~1220(32.0~122.0°F)
Temperature Offset
AV 15
R/W
Offset for Current
Temperature
°C: -100~100 (- 10.0~10.0°C)
°F: -180~180 (-18.0~18.0°F)
Proportional Band-
Stage Width
AV 16
R/W
Proportional Band or Stage
Width
°C :0~100 (00~10.0 °C)
°F: 0~180 (00~18.0 °F)
Stage Differential
AV 17
R/W
Stage Differential
°C :1~10 (0.1~1.0 °C)
°F: 1~18 (0.1~1.8 °F)
Lock
AV 18
RW
LOCK
Bit Definition:
0
: MODE button
(dec=1)
1
: Down button
(dec=2)
2
: Up button
(dec=4)
3
: FAN SPEED button
(dec=8)
4
: Power On/Off button
(dec=16)
5
: SET (or
℃
/
℉
) button
(dec=32)
6
: ESI contact
detection
(dec=64)
7
: Door/Window
contact detection
(dec=128)
8
: Modification for
communication
parameters
(dec=256)
i.e. baud rate, MAC addr,
device inst.
9
: Control DOs by
thermostat algorithm
(0) or BACnet sup. (1)
(dec=512)
10~15
: reserved/unused
Bit Value
0: Unlock / enable
1: Lock / disable
Examples (add dec values to
lock multiples) For more details
see Lock Function Setup and
Examples section of this manual