SETTING THE LIMIT VALUES
The limit values (switch off criteria) are set as follows:
Press key
and then key
2x. The display shows the following:
Press the <OK> key. The display shows the following:
After selection of the desired limit value
or
and pressing the key <OK> the limit value can be in-
creased or reduced with key
or
and then permanently saved with the <OK> key. In this context the
following settings are possible:
If you scroll beyond the highest settable value, the indication “deactivated” appears in the display. Note the
following upon saving this setting:
The limit values must be set according to the respective consumption habits. If under the normal consump-
tion habits a limit value is regularly exceeded without a leak being present, the corresponding limit value
can be reset to a larger value.
Hauptmenü
· Grenzwerte
Grenzwerte
· Max.Entn.menge
Limit value
Lowest
settable value
Default value
(Factory setting)
Highest
settable value
Step size
Maximum vol-
ume drawn
100 litre
500 litre
3000 litre,
deactivated
100 litre
(less than
1000 litre)
200 litre
(more than
1000 litre)
Maximum
volume flow
rate
10 litre/minute
65 litre/minute
100 litre/minute
deactivated
10 litre/minute
Maximum
drawing time
10 minutes
30 minutes
2 hours,
deactivated
10 minutes
If one of the limit values is deactivated, this value is no longer monitored. If for ex-
ample the maximum drawing time is deactivated, then a small leak can only be de-
tected by the leak protection system when the maximum water volume set for an-
other limit value is reached.